Inflection Point Engineering IPE-TM-510 Hydraulics

Typical Pump Spillback Hydraulics P9.8

IPE-TM-510-12

1. Table of Contents

1. Table of Contents 1

2. Purpose 1

3. Determine Pump Minimum Flow Protection Requirements 1

4. Normal Flow for All Process Cases Exceeds Pump Minimum Flow 2

5. Column Total Overhead Pump with Minimum Flow Protection via Reflux 6

APPENDIX A 12

APPENIDX B 13

2. Purpose

This procedure demonstrates the proper method of setting up the most common hydraulic circuits in P9.8 for pump minimum flow protection. In the hydraulic tabulations, for all flow scenarios in all process cases, the pump head and system frictional losses between the upstream vessel and spillback/splitter node must be based on a flow no lower than the minimum continuous flow of the pump.

3. Determine Pump Minimum Flow Protection Requirements

Tool (see Appendix A and B for graphical decision trees) shall be used to determine whether a pump requires minimum flow protection. If the Design Engineer concludes that pump minimum flow protection is required, the tool will indicate the section number and procedure number that shall be used as a guide to ensure that the hydraulic circuits are set up properly. All the simulation and flow scenario factors are calculated in Tool T-510-04, “Factors and Spillback Requirements for P98 Hydraulics”. The only required input to the tool is the pump minimum flow, normal process flows and specific gravity.

4. Normal Flow for All Process Cases Exceeds Pump Minimum Flow

This example involves a pump with a single discharge flow path and multiple process cases. At the normal flow scenario for each process case, the flow exceeds the minimum continuous flow of the pump and the spillback flow control valve is closed. At the alternate flow scenario of the lowest process flow case, the flow is less than the minimum continuous flow of the pump. An automated spillback is required where the spillback flow controller adjusts the opening of the spillback flow control valve until the flow through the pump equals or exceeds the minimum continuous flow. For the alternate flow scenario of the lowest process flow case, the flow through the pump and spillback control valve is equal to the minimum flow of the pump. If the forward flow control valve ever closes (due to a localized instrument air failure, for example), the spillback flow control valve must be capable of passing the minimum continuous flow of the pump.

The Design Engineer shall adhere to the following (see Example 4 hydraulic tabulations):

From Tool :

Example 4 Hydraulics of Pump with Single Discharge Flow Path and Minimum Flow Protection via Control Valve

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

SINGLE DISCHARGE – S/B WITH CV – CASE 1 without its written permission. EFID

Circuit 1: FRESH FEED Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FEED SURGE DRUM 10 29.0 29.0 29.0

Liquid Level 0 -0.15 29.0 -0.15 29.0 -0.15 29.0

Line 1 (Alter%= 87.2) 8 3.7 0.09 0.32 29.1 0.39 29.1 0.25 29.1

Static Head 7 -2.19 28.8 -2.19 28.8 -2.19 28.9

CHARGE PUMP *Gov* 2 -486.4 31.0 -466.5 30.9 -509.1 31.1

Pump head, feet 1641.7 1574.6 1718.5

Pump capacity, gpm 439 483 383

Flowing Specific Gravity 0.684

Operating Temperature, degF 201

Viscosity, cp 0.27

Line 3 (Alter%= 87.2) 6 3.3 0.35 1.14 517.4 1.38 497.4 0.88 540.2

CHARGE PUMP SPILLBACK FE(1701) 6 1.49 516.3 1.80 496.0 0.24 539.3

Line 4 (Alter%= 87.2) 6 .47 0.35 0.17 514.8 0.20 494.2 0.13 539.1

CHARGE PUMP SPILLBACK SPLIT POINT 514.6 494.0 539.0

Line 5 6 .47 0.35 0.17 514.6 0.20 494.0 0.03 539.0

FRESH FEED ORIFICE FE(1702) 6 1.49 514.4 1.80 493.8 0.24 538.9

Line 20 6 1.7 0.35 0.58 512.9 0.70 492.0 0.09 538.7

FRESH FEED CV(1602) 49.52 512.4 10.02 491.3 95.70 538.6

Line 21 6 2.4 0.35 0.84 462.9 1.02 481.3 0.13 442.9

FRESH FEED ADDITION POINT 462.0 480.3 442.8

Circuit 2: CHARGE PUMP MINIMUM FLOW SPILLBACK Case Design Case Alternate

Press 100.0% .0% 100.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

CHARGE PUMP SPILLBACK SPLIT POINT 514.6 539.0

Line 8 (Flow %= 87.2) 6 2.4 0.27 0.65 514.6 0.65 539.0

CHARGE PUMP SPILLBACK CV(1601) 481.90 514.0 506.25 538.3

Line 9 (Flow %= 87.2) 6 2.4 0.27 0.65 32.1 0.65 32.1

Static Head 10 2.23 31.4 2.23 31.4

Liquid Level 0 0.15 29.2 0.15 29.2

FEED SURGE DRUM 10 29.0 29.0

Example 4 (continued)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

SINGLE DISCHARGE – S/B WITH CV – CASE 2 without its written permission. EFID

Circuit 1: FRESH FEED Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FEED SURGE DRUM 10 29.0 29.0 29.0

Liquid Level 0 -0.15 29.0 -0.15 29.0 -0.15 29.0

Line 1 (Alter%= 87.2) 8 3.7 0.09 0.32 29.2 0.38 29.2 0.24 29.2

Static Head 7 -2.23 28.8 -2.23 28.8 -2.23 28.9

CHARGE PUMP 2 -500.0 31.1 -480.7 31.0 -521.1 31.1

Pump head, feet 1653.8 1589.3 1723.6

Pump capacity, gpm 430 473 375

Flowing Specific Gravity 0.698

Operating Temperature, degF 212

Viscosity, cp 0.27

Line 3 (Alter%= 87.2) 6 3.3 0.34 1.12 531.1 1.35 511.7 0.86 552.2

CHARGE PUMP SPILLBACK FE(1701) 6 1.46 530.0 1.77 510.4 0.23 551.3

Line 4 (Alter%= 87.2) 6 .47 0.34 0.16 528.5 0.20 508.2 0.13 551.1

CHARGE PUMP SPILLBACK SPLIT POINT 528.4 508.0 551.0

Line 5 6 .47 0.34 0.16 528.4 0.20 508.0 0.03 551.0

FRESH FEED ORIFICE FE(1702) 6 1.46 528.2 1.77 507.8 0.23 551.0

Line 20 6 1.7 0.34 0.56 526.7 0.68 506.0 0.09 550.8

FRESH FEED CV(1602) 69.56 526.2 28.33 505.3 125.90 550.7

Line 21 6 2.4 0.34 0.82 456.6 0.99 477.0 0.13 424.8

FRESH FEED ADDITION POINT 455.8 476.0 424.7

Circuit 2: CHARGE PUMP MINIMUM FLOW SPILLBACK Case Design Case Alternate

Press 100.0% .0% 100.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

CHARGE PUMP SPILLBACK SPLIT POINT 528.4 551.0

Line 8 (Flow %= 87.2) 6 2.4 0.27 0.64 528.4 0.64 551.0

CHARGE PUMP SPILLBACK CV(1601) 495.57 527.8 518.30 550.4

Line 9 (Flow %= 87.2) 6 2.4 0.27 0.64 32.1 0.64 32.1

Static Head 10 2.23 31.4 2.23 31.4

Liquid Level 0 0.15 29.2 0.15 29.2

FEED SURGE DRUM 10 29.0 29.0

5. Column Total Overhead Pump with Minimum Flow Protection via Reflux

This example involves a column total overhead pump with multiple process cases. At the normal (100%) flow scenario for each process case, the process flow exceeds the minimum continuous flow of the pump. An automated spillback is not required in column total overhead liquid service when – for all process cases – the sum of the normal (100%) reflux flow and turndown flow of net overhead liquid exceeds the minimum continuous flow of the pump.

The Design Engineer shall adhere to the following (see Example 5 hydraulic tabulations):

From Tool :

Example 5 Hydraulics of Column Total Overhead Pumps with Minimum Flow Protection via Reflux

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

COLUMN OVERHEAD – NO S/B WITH CV CASE CASE 1 without its written permission. EFID

Circuit 31: TOLUENE COLUMN NET OVERHEAD Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

TOLUENE COLUMN RECEIVER 22 40.0 36.9 49.6

Liquid Level 2 -0.48 40.0 -0.48 36.9 -0.48 49.6

Line 1 (Alter%= 66.3) 12 5.3 0.09 0.47 40.5 0.56 37.3 0.21 50.1

Static Head 19 -6.05 40.0 -6.05 36.8 -6.05 49.9

TOLUENE COLUMN OVERHEAD PUMPS 3 -107.9 46.1 -104.5 42.8 -116.7 55.9

Pump head, feet 344.5 333.85 372.92

Pump capacity, gpm 1261 1387 836

Flowing Specific Gravity 0.723

Operating Temperature, degF 328

Viscosity, cp 0.20

Line 2 (Alter%= 66.3) 8 3.4 0.70 2.39 153.9 2.89 147.3 1.05 172.7

REFLUX + NET OVERHEAD SPLITTER 3 151.5 144.4 171.6

Line 6 3 .63 0.36 0.23 151.5 0.27 144.4 0.08 171.6

Static Head 37 11.62 151.3 11.62 144.2 11.62 171.5

TOLUENE PRODUCT COOLER 40 4.00 139.7 4.84 132.6 1.44 159.9

Line 321 3 2.2 0.33 0.73 135.7 0.88 127.7 0.26 158.5

Static Head 35 -12.76 135.0 -12.76 126.8 -12.76 158.2

TOLUENE PRODUCT TRIM COOLER 5 4.00 147.7 4.84 139.6 1.44 171.0

Line 322 3 2.2 0.33 0.73 143.7 0.89 134.8 0.26 169.5

Static Head 5 -1.84 143.0 -1.84 133.9 -1.84 169.3

TOLUENE COLUMN NET OVHD FE(1733) 3 1.75 144.8 2.12 135.7 0.63 171.1

Line 323 3 1.1 0.33 0.37 143.1 0.45 133.6 0.13 170.5

TOLUENE COLUMN NET OHD CV(1673) 120.81 142.7 110.84 133.2 149.68 170.4

Line 324 3 5.7 0.33 1.91 21.9 2.31 22.3 0.69 20.7

TOLUENE COLUMN OVERHEAD B.L. 20.0 20.0 20.0

Example 5 (Continued)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

COLUMN OVERHEAD – NO S/B WITH CV CASE CASE 1 without its written permission. EFID

Circuit 32: TOLUENE COLUMN REFLUX Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

TOLUENE COLUMN RECEIVER 22 40.0 36.9 49.6

Liquid Level 2 -0.48 40.0 -0.48 36.9 -0.48 49.6

Line 1 (Alter%= 66.3) 12 5.3 0.09 0.47 40.5 0.56 37.3 0.21 50.1

Static Head 19 -6.05 40.0 -6.05 36.8 -6.05 49.9

TOLUENE COLUMN OVERHEAD PUMPS 3 -107.9 46.1 -104.5 42.8 -116.7 55.9

Pump head, feet 344.5 333.85 372.92

Pump capacity, gpm 1261 1387 836

Flowing Specific Gravity 0.723

Operating Temperature, degF 328

Viscosity, cp 0.20

Line 2 (Alter%= 66.3) 8 3.4 0.70 2.39 153.9 2.89 147.3 1.05 172.7

REFLUX + NET OVERHEAD SPLITTER 3 151.5 144.4 171.6

Line 5 (Alter%= 69.3) 8 2.4 0.32 0.77 151.5 0.93 144.4 0.37 171.6

Static Head 3 -0.94 150.8 -0.94 143.5 -0.94 171.3

TOLUENE COLUMN REFLUX FE(1732) 8 1.08 151.7 1.31 144.5 0.39 172.2

Line 315 (Alter%= 69.3) 8 2.4 0.32 0.77 150.6 0.93 143.2 0.37 171.8

TOLUENE COLUMN REFLUX CV(1672) 32.73 149.9 24.79 142.2 55.03 171.4

Line 316 (Alter%= 69.3) 8 4.3 0.32 1.40 117.1 1.70 117.4 0.67 116.4

Static Head 194 60.74 115.7 60.74 115.7 60.74 115.7

TOLUENE COLUMN 194 55.0 55.0 55.0

Example 5 (Continued)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

COLUMN OVERHEAD – NO S/B WITH CV CASE CASE 2 without its written permission. EFID

Circuit 31: TOLUENE COLUMN NET OVERHEAD Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

TOLUENE COLUMN RECEIVER 22 40.0 36.9 49.6

Liquid Level 2 -0.48 40.0 -0.48 36.9 -0.48 49.6

Line 1 (Alter%= 66.3) 12 5.3 0.11 0.60 40.5 0.72 37.3 0.26 50.1

Static Head 19 -6.05 39.9 -6.05 36.6 -6.05 49.8

TOLUENE COLUMN OVERHEAD PUMPS *Gov* 3 -103.4 45.9 -99.13 42.7 -114.8 55.9

Pump head, feet 330.1 316.64 366.62

Pump capacity, gpm 1429 1572 948

Flowing Specific Gravity 0.723

Operating Temperature, degF 328

Viscosity, cp 0.20

Line 2 (Alter%= 66.3) 8 3.4 0.90 3.06 149.3 3.70 141.8 1.34 170.6

REFLUX + NET OVERHEAD SPLITTER 3 146.2 138.1 169.3

Line 6 3 .63 0.36 0.23 146.2 0.27 138.1 0.08 169.3

Static Head 37 11.62 146.0 11.62 137.8 11.62 169.2

TOLUENE PRODUCT COOLER 40 4.00 134.4 4.84 126.2 1.44 157.6

Line 321 3 2.2 0.33 0.73 130.4 0.88 121.4 0.26 156.2

Static Head 35 -12.76 129.7 -12.76 120.5 -12.76 155.9

TOLUENE PRODUCT TRIM COOLER 5 4.00 142.4 4.84 133.2 1.44 168.7

Line 322 3 2.2 0.33 0.73 138.4 0.89 128.4 0.26 167.2

Static Head 5 -1.84 137.7 -1.84 127.5 -1.84 167.0

TOLUENE COLUMN NET OVHD FE(1733) 3 1.75 139.5 2.12 129.4 0.63 168.8

Line 323 3 1.1 0.33 0.37 137.8 0.45 127.2 0.13 168.2

TOLUENE COLUMN NET OHD CV(1673) 115.51 137.4 104.48 126.8 147.35 168.0

Line 324 3 5.7 0.33 1.91 21.9 2.31 22.3 0.69 20.7

TOLUENE COLUMN OVERHEAD B.L. 20.0 20.0 20.0

Example 5 (Continued)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY CITY, STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

COLUMN OVERHEAD – NO S/B WITH CV CASE CASE 2 without its written permission. EFID

Circuit 32: TOLUENE COLUMN REFLUX Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

TOLUENE COLUMN RECEIVER 22 40.0 36.9 49.6

Liquid Level 2 -0.48 40.0 -0.48 36.9 -0.48 49.6

Line 1 (Alter%= 66.3) 12 5.3 0.11 0.60 40.5 0.72 37.3 0.26 50.1

Static Head 19 -6.05 39.9 -6.05 36.6 -6.05 49.8

TOLUENE COLUMN OVERHEAD PUMPS *Gov* 3 -103.4 45.9 -99.13 42.7 -114.8 55.9

Pump head, feet 330.1 316.64 366.62

Pump capacity, gpm 1429 1572 948

Flowing Specific Gravity 0.723

Operating Temperature, degF 328

Viscosity, cp 0.20

Line 2 (Alter%= 66.3) 8 3.4 0.90 3.06 149.3 3.70 141.8 1.34 170.6

REFLUX + NET OVERHEAD SPLITTER 3 146.2 138.1 169.3

Line 5 (Alter%= 69.3) 8 2.4 0.40 0.95 146.2 1.15 138.1 0.46 169.3

Static Head 3 -0.94 145.3 -0.94 136.9 -0.94 168.8

TOLUENE COLUMN REFLUX FE(1732) 8 1.35 146.2 1.63 137.9 0.48 169.8

Line 315 (Alter%= 69.3) 8 2.4 0.40 0.95 144.9 1.15 136.3 0.46 169.3

TOLUENE COLUMN REFLUX CV(1672) 26.45 143.9 17.25 135.1 52.27 168.8

Line 316 (Alter%= 69.3) 8 4.3 0.40 1.74 117.5 2.11 117.8 0.84 116.6

Static Head 194 60.73 115.7 60.73 115.7 60.73 115.7

TOLUENE COLUMN 194 55.0 55.0 55.0

APPENDIX A

DECISION TREE A - Automated Pump Spillbacks

APPENIDX B

DECISION TREE B - Automated Spillbacks Associated with Column Total Overhead Pumps