Inflection Point Engineering IPE-TM-510 Hydraulics

Hydraulics for Fractionation Overhead Systems

IPE-TM-510-10

1. Purpose

This Procedure demonstrates the proper method of setting up the hydraulic circuits for a fractionation column equipped with a total condensing system, an elevated condenser, and a hot vapor bypass. See the example hydraulic tabulations and Figure 1, “Fractionator Overhead Schematic”.

2. General

When a fractionation column is equipped with a total condensing system, an elevated condenser, and a hot vapor bypass control valve, the overhead pressure of the column is controlled by adjusting the opening of the control valve at the condenser inlet. The differential pressure through the hot vapor bypass is controlled by adjusting the opening of the hot vapor bypass control valve. The differential pressure shall be determined by the Design Engineer after reviewing the technology specific design manual if applicable, and Procedure Section 6.2. The receiver pressure varies slightly with flow through the hot vapor bypass. The flow rate through the hot vapor bypass is based on the estimated vapor rate required to makeup for the condensation of overhead material in the receiver due to heat loss.

3. P9.8 Hydraulics Program

To properly model this scenario with the P9.8 hydraulics program, a dummy circuit shall run first. In the dummy circuit, the hot vapor bypass control valve shall be modeled as a miscellaneous piece of equipment with a constant differential pressure. Despite the gas phase application, the differential pressure shall be entered as static head; otherwise, the P9.8 Hydraulics program will vary the differential pressure with the flow rate of each process simulation case. This circuit calculates and stores the receiver pressures at the normal, design, and alternate condition of each process simulation case.

The dummy circuit shall not be included in the Engineering Design Information (EDI) that is given to the customer.

Please note that the flow through the hot vapor bypass control valve is based on six mass percent of the total overhead vapor at the outlet nozzle of the fractionation column. To avoid adding extra margin to the already conservative ‘six mass percent’ basis, the design condition of the hot vapor bypass circuits shall be set to 100%.

Next, the dummy circuit shall be copied. The word ‘dummy’ in the new circuit title shall be deleted. The miscellaneous piece of equipment shall be replaced with a control valve equipment number. The instrument engineer shall use this equipment number to size and specify the hot vapor bypass control valve. The new circuit shall run second. This circuit shall be included in the Engineering Design Information (EDI) that is given to the customer.

The column overhead circuit through the condenser shall run last. Because the receiver pressures were calculated and stored when the hot vapor bypass circuit ran, the P9.8 hydraulics program is now able to accurately calculate the pressure downstream of the pressure control valve at the condenser inlet. Confirm that the receiver hydraulic pressures are greater than the vapor pressure.

Example 1 and Figure 1 shall be used as a guide when setting up the hydraulic circuits.

4. New Hydraulics Program

To properly model this scenario with the new hydraulics program, the hot vapor bypass circuit shall run first. This circuit calculates and stores the receiver pressures at the normal, design, and alternate condition of each process simulation case.

The column overhead circuit through the condenser shall run last. Because the receiver pressures were calculated and stored when the hot vapor bypass circuit ran, the new hydraulics program is now able to accurately calculate the pressure downstream of the pressure control valve (hydraulic balance) at the condenser inlet.

Example 2 and Figure 1 shall be used as a guide when setting up the hydraulic circuits.

Setting Up the Control Valve In the Hot Vapor Bypass Circuit

Additional Information for Hot Vapor Bypass Circuit

Information for Column Overhead Circuit

Example 1: Hydraulics of Column Total Condensing System with Hot Vapor Bypass (P9.8 Hydraulics Program)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY , STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

CASE 1 without its written permission. EFID

Circuit 1: FRACTIONATION COLUMN VAPOR BYPASS (DUMMY) Case Design Case Alternate

Press 100.0% 100.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FRACTIONATION COLUMN 216 103.0 103.0 103.0

Line 1 (Desgn%=110.0) 24 10 0.14 1.40 103.0 1.69 103.0 0.50 103.0

OVHD VAPOR SPL – VAPOR BYPASS 40 101.6 101.3 102.5

Line 5 (Flow%=6.0) ‡ 12 4.8 0.14 0.67 101.6 0.67 101.3 0.24 102.5

VAPOR BYPASS DUMMY CV(1251) § 100.9 100.6 102.3

Static Head 11.00 100.9 11.00 100.6 11.00 102.3

Line 6 (Flow%=6.0) ‡ 12 1.7 0.14 0.24 89.9 0.24 89.6 0.09 91.3

FRACTIONATION COLUMN RECEIVER 30 89.7 89.4 91.2

Circuit 2: FRACTIONATION COLUMN VAPOR BYPASS Case Design Case Alternate

Press 100.0% 100.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FRACTIONATION COLUMN 216 103.0 103.0 103.0

Line 1 (Desgn%=110.0) 24 10 0.14 1.40 103.0 1.69 103.0 0.50 103.0

OVHD VAPOR SPL – VAPOR BYPASS 40 101.6 101.3 102.5

Line 5 (Flow%=6.0) ‡ 12 4.8 0.14 0.67 101.6 0.67 101.3 0.24 102.5

VAPOR BYPASS CV(1601) 11.00 100.9 11.00 100.6 11.00 102.3

Line 6 (Flow%=6.0) ‡ 12 1.7 0.14 0.24 89.9 0.24 89.6 0.09 91.3

FRACTIONATION COLUMN RECEIVER 30 89.7 89.4 91.2

Circuit 3: FRACTIONATION COLUMN OVERHEAD Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

OVHD VAPOR SPL – VAPOR BYPASS 40 101.6 101.3 102.5

Line 2 24 3.4 0.14 0.48 101.6 0.58 101.3 0.17 102.5

OVERHEAD PRESSURE CV(1602) 5.68 101.1 4.37 100.7 9.09 102.3

Line 3 24 2.8 0.14 0.39 95.5 0.47 96.4 0.14 93.2

CONDENSER 40 4.84 95.1 5.86 95.9 1.74 93.1

Line 4 12 3.7 0.14 0.52 90.2 0.63 90.0 0.19 91.4

FRACTIONATION COLUMN RECEIVER 30 89.7 89.4 91.2

‡ This piping segment shall reference the stream in the heat and weight balance corresponding to the total overhead vapor from the column.

§ This is a miscellaneous piece of equipment. The differential pressure is determined by the process engineer and shall be identical for all process simulation cases. Despite the gas phase application, the differential pressure shall be modeled as static head.

Example 1: Hydraulics of Column Total Condensing System with Hot Vapor Bypass (P9.8 Hydraulics Program) (cont’d)

ANY CLIENT Note - the information in this document is Page

XXXXXX PROJECT confidential and the property of Inflection Point Engineering, and Date

ANY , STATE must not be disclosed to others or reproduced in Proj

COUNTRY any manner or used for any purpose whatsoever By

CASE 2 without its written permission. EFID

Circuit 1: FRACTIONATION COLUMN VAPOR BYPASS (DUMMY) Case Design Case Alternate

Press 100.0% 100.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FRACTIONATION COLUMN 216 103.0 103.0 103.0

Line 1 (Desgn%=110.0) 24 10 0.15 1.50 103.0 1.82 103.0 0.54 103.0

OVHD VAPOR SPL – VAPOR BYPASS 40 101.5 101.2 102.5

Line 5 (Flow%=6.0) ‡ 12 4.8 0.15 0.72 101.5 0.72 101.2 0.26 102.5

VAPOR BYPASS DUMMY CV(1251) § 100.8 100.5 102.2

Static Head 11.00 100.8 11.00 100.5 11.00 102.2

Line 6 (Flow%=6.0) ‡ 12 1.7 0.15 0.26 89.8 0.26 89.5 0.09 91.2

FRACTIONATION COLUMN RECEIVER 30 89.5 89.2 91.1

Circuit 2: FRACTIONATION COLUMN VAPOR BYPASS Case Design Case Alternate

Press 100.0% 100.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

FRACTIONATION COLUMN 216 103.0 103.0 103.0

Line 1 (Desgn%=110.0) 24 10 0.15 1.50 103.0 1.82 103.0 0.54 103.0

OVHD VAPOR SPL – VAPOR BYPASS 40 101.5 101.2 102.5

Line 5 (Flow%=6.0) ‡ 12 4.8 0.15 0.72 101.5 0.72 101.2 0.26 102.5

VAPOR BYPASS CV(1601) 11.00 100.8 11.00 100.5 11.00 102.2

Line 6 (Flow%=6.0) ‡ 12 1.7 0.15 0.26 89.8 0.26 89.5 0.09 91.2

FRACTIONATION COLUMN RECEIVER 30 89.5 89.2 91.1

Circuit 3: FRACTIONATION COLUMN OVERHEAD Case Design Case Alternate

Press 100.0% 110.0% 60.0%

Drop --------------- --------------- ---------------

Line 100 Per Nozl Press Inlet Press Inlet Press Inlet

Size Eq 100ft Elev Drop Press Drop Press Drop Press

Equipment Identification in ft psi ft psi psig psi psig psi psig

OVHD VAPOR SPL – VAPOR BYPASS 40 101.5 101.2 102.5

Line 2 24 3.4 0.15 0.51 101.5 0.62 101.2 0.18 102.5

OVERHEAD PRESSURE CV(1602) 5.49 101.0 4.12 100.6 9.02 102.3

Line 3 24 2.8 0.15 0.42 95.5 0.51 96.4 0.15 93.3

CONDENSER 40 5.00 95.1 6.05 95.9 1.80 93.1

Line 4 12 3.7 0.15 0.56 90.1 0.68 89.9 0.20 91.3

FRACTIONATION COLUMN RECEIVER 30 89.5 89.2 91.1

‡ This piping segment shall reference the stream in the heat and weight balance corresponding to the total overhead vapor from the column.

§ This is a miscellaneous piece of equipment. The differential pressure is determined by the process engineer and shall be identical for all process data cases. Despite the gas phase application, the differential pressure shall be modeled as static head.

Example 2: Hydraulics of Column Total Condensing System with Hot Vapor Bypass (New Hydraulics Program)

Circuit 2 : Fractionation Column Hot Vapor Bypass

Normal Design Alternate

PRESS 100.0% 100.0% 50.0%

DROP ------------------- ------------------- -------------------

LINE 100 PER NOZL PRESS INLET PRESS INLET PRESS INLET

SIZE EQ 100ft ELEV DROP PRESS DROP PRESS DROP PRESS

EQUIPMENT IDENTIFICATION IN ft psi ft psi psig psi psig psi psig

Fractionation Column 143.7 256.0 256.0 256.0

LN-XP-655(Des=110%) 24 1.45 0.38 0.55 256.0 0.67 256.0 0.14 256.0

Overhead Vapor - Hot Vapor Bypass Split 138.7 255.4 255.3 255.9

LN-657 8 3.24 0.36 1.17 255.4 1.17 255.3 0.29 255.9

Hot Vapor Bypass PDIC: CV-1644 50.9 8.00 254.3 8.00 254.2 8.00 255.6

LN-658 8 0.63 0.37 0.24 246.3 0.24 246.2 0.06 247.6

Receiver 45.9 246.0 245.9 247.5

Notes:

The receiver vapor pressure = 245 psig

The inlet/outlet streams for the PDIC were already at 6% of overhead stream

Circuit 3 : Fractionation Overhead

Normal Design Alternate

PRESS 100.0% 110.0% 50.0%

DROP ------------------- ------------------- -------------------

LINE 100 PER NOZL PRESS INLET PRESS INLET PRESS INLET

SIZE EQ 100ft ELEV DROP PRESS DROP PRESS DROP PRESS

EQUIPMENT IDENTIFICATION IN ft psi ft psi psig psi psig psi psig

Overhead Vapor - Hot Vapor Bypass Split 138.7 255.4 255.3 255.9

LN-670 24 6.52 0.38 2.51 255.4 3.03 255.3 0.63 255.9

Overhead CV-1648 56.0 3.14 252.9 1.82 252.3 6.78 255.2

LN-670A 24 1.45 0.38 0.56 249.8 0.68 250.5 0.14 248.5

Condenser (Shell) 51.0 3.00 249.2 3.63 249.8 0.75 248.3

LN-XP-656 18 1.13 0.18 0.20 246.2 0.24 246.2 0.05 247.6

Receiver(Des=100%) 45.9 246.0 245.9 247.5

Example 2: Hydraulics of Column Total Condensing System with Hot Vapor Bypass (New Hydraulics Program) (cont’d)

Circuit 2 : Fractionation Column Hot Vapor Bypass

Normal Design Alternate

PRESS 100.0% 100.0% 50.0%

DROP ------------------- ------------------- -------------------

LINE 100 PER NOZL PRESS INLET PRESS INLET PRESS INLET

SIZE EQ 100ft ELEV DROP PRESS DROP PRESS DROP PRESS

EQUIPMENT IDENTIFICATION IN ft psi ft psi psig psi psig psi psig

Fractionation Column 143.7 256.0 256.0 256.0

LN-XP-655(Des=110%) 24 1.45 0.37 0.54 256.0 0.66 256.0 0.14 256.0

Overhead Vapor - Hot Vapor Bypass Split 138.7 255.5 255.3 255.9

LN-657 8 3.24 0.36 1.16 255.5 1.16 255.3 0.29 255.9

Hot Vapor Bypass PDIC: CV-1644 50.9 8.00 254.3 8.00 254.2 8.00 255.6

LN-658 8 0.63 0.37 0.23 246.3 0.23 246.2 0.06 247.6

Receiver 45.9 246.1 245.9 247.5

Notes:

The receiver vapor pressure = 245 psig

The inlet/outlet streams for the PDIC were already at 6% of overhead stream

Circuit 3 : Fractionation Overhead

Normal Design Alternate

PRESS 100.0% 110.0% 50.0%

DROP ------------------- ------------------- -------------------

LINE 100 PER NOZL PRESS INLET PRESS INLET PRESS INLET

SIZE EQ 100ft ELEV DROP PRESS DROP PRESS DROP PRESS

EQUIPMENT IDENTIFICATION IN ft psi ft psi psig psi psig psi psig

Overhead Vapor - Hot Vapor Bypass Split 138.7 255.5 255.3 255.9

LN-670 24 6.52 0.38 2.49 255.5 3.01 255.3 0.62 255.9

Overhead CV-1648 56.0 3.19 253.0 1.89 252.3 6.80 255.2

LN-670A 24 1.45 0.38 0.55 249.8 0.67 250.4 0.14 248.4

Condenser (Shell) 51.0 2.96 249.2 3.58 249.8 0.74 248.3

LN-XP-656 18 1.13 0.17 0.20 246.3 0.24 246.2 0.05 247.6

Receiver(Des=100%) 45.9 246.1 245.9 247.5

Figure 1 Fractionator Overhead Schematic