Inflection Point Engineering IPE-TM-400 Heat Exchangers

Vent Condensers

IPE-TM-400-13

1. Table of Contents

2. Purpose

This procedure describes the guidelines to be followed for the design and specification of vent condensers.

3. General Discussion

There is no official definition of the term “vent condenser”. However at Inflection Point Engineering this term has normally been applied to three general types of heat exchangers. All three types partially or totally condense an all vapor feed stream.

3.1 Refluxed Condenser

The product liquid exits the exchanger through the same line that provides feed to the exchanger.

3.2 Flow-Through Condenser

The product liquid exits the exchanger through the same line as the product vapor. A down stream separation device is then used to produce a vapor product, a hydrocarbon liquid product and, if present, a liquid water product.

3.3 Exchanger-Separator Condenser

The product liquid exits the exchanger through a line that is not used by the feed or the vapor product.

For most vent condensers the liquid product is routed back to an upstream receiver that is providing the vapor that is feeding the vent condenser. Some of the condensed liquid will normally re-vaporize and hence return to the vent condenser. This recirculation will build to a rate determined by the compositions and the temperature difference across the exchanger. A large temperature difference across the vent condenser can result in an unacceptably large recirculation rate. For wet (water containing) systems water can be the major cause of a high recirculation rate. This can be avoided if a water product is produced from the upstream receiver or if liquid water produced from the exchanger is not returned to the upstream receiver.

Often a vent condenser is immediately upstream of a vacuum system and the performance of the vent condenser is critical for the performance of the vacuum system. The vacuum system may be an ejector based vacuum system or a vacuum pump system. Regardless of the type of vacuum system, a Inflection Point Engineering heat exchanger specification is produced for the vent condenser. For an ejector based system the vent condenser supply is normally in the scope for the ejector system supplier. This is to be indicated in both the Inflection Point Engineering heat exchanger specification and the Inflection Point Engineering vacuum system specification.

4. Condensed Liquid Exits through Vapor Feed Line (Refluxed Condenser)

This type of vent condenser can be built with a horizontal exchanger above the receiver or with a vertical exchanger mounted directly to the receiver. A horizontal exchanger will have the cooling medium on the tube side while the vertical exchanger will have the cooling medium on the shell side. If the cooling medium is relatively dirty a horizontal configuration is advantageous because the vertical arrangement does not have a removable bundle to facilitate cleaning of the shellside.

These configurations normally can not be used for wet systems with the receiver being too hot to form a liquid water phase. The recycle rate of the water between the receiver and the vent condenser would be unacceptably high.

The inlet vapor velocity must be low enough so that the condensed liquid can gravity flow against the inlet vapor. This requires that the exchanger and inlet line are sized for very low pressure drops.

4.1 Horizontal Vent Condenser Draining to Upstream Receiver

Figure 4.1 is a section of an old PID module. This shows a horizontal shell and tube vent condenser located above a column receiver.

Figure 4.1

Horizontal Vent Condenser above a Receiver

a. Some key features of this design are:

Procedure has more information on these equations. The first equation is based on ’s law and is likely applicable to systems with atmospheric and higher pressures. The second equation is based on the Intermediate Law and is likely applicable for vacuum systems.

b. Advantages:

c. Disadvantages:

4.2 Horizontal Vent Condenser Draining to Location Other Than the Upstream Receiver

In some cases, some or all of the liquid from the vent condenser goes to a destination other than the receiver. In these cases, the vapor from the receiver goes into the branch connection of a tee and then up into the inlet of the vent condenser. The bottom connection of the tee (straight connection) is the liquid drain. The liquid drain line will maintain the sizing of the bidirectional flow line per the equations in section 4.1 for at least 3 ft (1000 mm) below the tee to allow vapors to disengage. The liquid lines below the swage should be sized for self-venting flow.

Figure 4.2 is an example of a vent condenser where the liquid drains to a location other than the upstream receiver. This arrangement has been used in the Fractionation Section of Phenol Units.

Figure 4.2

Horizontal Vent Condenser above a Receiver

where liquid drains to another location

The ultimate destination of the liquid is typically at a higher pressure than the vent condenser so the elevation of the tee must be sufficient to allow the system to balance hydraulically. Any instruments in this line (flow meters and/or control valves) must be located below the elevation of the final destination to ensure that there is only liquid in them.

Liquid lines are self-venting if the liquid velocity is less than the following:

4.3 Vertical Vent Condenser Directly Attached to Receiver

Figure 4.3 is a section of the PID module . This shows a vertical vent condenser that is directly attached to a column receiver.

Figure 4.3

Vertical Vent Condenser Directly Attached to Receiver

a. Some key features of this design are:

b. Advantages:

c. Disadvantages:

5. Condensed Liquid Exits with Vapor (Flow-Through Condenser)

Figure 5.1 is a section of PID module This shows a vent condenser with the liquid exiting through the vapor exit line. The exiting material goes to a three phase separator. The water is removed from the system and the hydrocarbon liquid is returned to the upstream receiver.

Figure 5.1

Liquid Exits with Vapor

Having the condensed liquid exit with the product vapor has several advantages over the condensed liquid exiting through the vapor inlet line.

The liquid return line from the separator has sometimes had a high loop to attempt to hold a liquid level in the separator. An open ended pipe distributor in the receiver should be used to keep a liquid seal and avoid receiver vapor from by-passing the vent condenser. The vent condenser rundown line should be sized like the rundown line from a standard condenser.

a. Advantages:

b. Disadvantages:

6. Condensed Liquid Exits through Separate Line (Exchanger-Separator Condenser)

This type of vent condenser functions both as an exchanger and a vapor-liquid separator. Normally no liquid level control is used for this system. Sometimes a high loop has been used on the liquid outlet line in an effort to hold a liquid level in the exchanger-separator. The main use of this configuration is when the outlet vapor goes to vacuum producing equipment. The liquid static head is normally used to allow the liquid to flow to a destination pressure that is significantly higher than the vapor inlet pressure.

a. Advantages:

b. Disadvantages:

6.1 Exchanger-Separator with Boot

Figure 6.1 is a section of a PID that shows an exchanger-separator with a boot. While such systems have been specified in the past, there is presently no justified use of this configuration. The condenser elevation must be sufficient to allow the liquid to flow to a destination with a pressure that is higher than the source pressure of the inlet vapor.

Figure 6.1

Liquid Boot on Vent Gas Condenser

6.2 Exchanger-Separator without Boot

Figure 6.2 is a section of the PID that shows an exchanger-separator without a boot. This configuration is used when the vapor goes to vacuum producing equipment. The condenser elevation must be sufficient to allow the liquid to flow to a destination with a pressure that is higher than the source pressure of the inlet vapor.

Figure 6.2

Vent Gas Condenser with Liquid from Bottom of Shell