IPE-TM-320 Fractionation
IPE-TM-320-14
This procedure provides the basis and methods for calculating column vapor/liquid loadings for tray and packing designs.
There is always a degree of uncertainty regarding the design loads of a new column. Actual operation may vary from the design due to feedstock changes, different product quality requirements, or new production needs. Therefore, some overage in column design is reasonable and appropriate. However, per Inflection Point Engineering policy, provide overage in the design reflux rate and the design percentage of flood. Do not provide overage in the load calculations. Use the largest theoretical loads for tray design.
The theoretical stage with the highest Vload has the governing vapor load for a column section.
Where:
QV : volumetric flow rate of vapor
V : density of vapor
L : density of liquid
The theoretical stage with the highest volumetric flow rate of liquid has the governing liquid load for a column section.
Most columns have more than one section, with each section having its own tray design. This occurs in the following cases:
When available, column loadings are generally obtained from an equilibrium stage model of the column. Care is needed to confirm that the modeling work provides appropriate loads at feed an energy removal or addition areas. The modeling of these areas, when poorly done, may result in erroneous loads being reported.
Thermosyphon reboilers are normally modeled as shown in Figure 1. A thermosyphon reboiler should produce a higher load, compared to a once through reboiler, for the same duty. The difference will be a function of the temperature difference across the reboiler. The larger the temperature difference, the larger the loading variation will be.
Preferential once through reboilers will have loading that are almost identical to an absolute once through reboiler.
Figure 1
Thermosyphon Reboiler
The reboiler return material produces vapor stream 7 and liquid stream 8. Bottom tray liquid 1 and reboiler liquid 8 combine to produce vapor stream 2 and total bottoms liquid 3. The vapor to the bottom tray is then the total of streams 2 and 7.
The third source of column loadings is the heat and weight balance. In some cases the governing loadings will be the vapor from and the liquid to the column top or the liquid from and the vapor to the column bottom. For example, this may be true for absorbers or strippers. Also special start-up and shutdown cases need to be considered. Sometimes downcomers need to be designed to accommodate large amounts of liquid during these special operations.
Figure 2 shows a sketch a column top.
Figure 2
Figure 3 shows a sketch of a column bottom.
Figure 3
8.2 Subscripts
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.
© 2026 Inflection Point Engineering, LLC. All rights reserved.