Inflection Point Engineering Scripts & Utilities

Cable Schedule Validator

NEC 310-based sanity checks on a cable schedule. Validates ampacity (NEC 310.16, 75°C Cu/Al), 125% continuous-load derate (NEC 210.19/215.2/430.22), 3% feeder voltage drop (NEC 215.2(A)(1) informational), and required field completeness.

References: NEC 310.16 (ampacity, 75°C column, 3 CCCs in raceway, 30°C ambient); NEC 210.19, 215.2, 430.22 (continuous-load 125%); NEC 215.2(A)(1) informational note (3% feeder voltage drop); NEC Chapter 9 Table 8 (conductor resistance). Voltage drop uses 3-phase approximation: VD = √3 · R · (L/1000) · I / Nsets.