Reference Tables
Allowable ampacities per NEC Table 310.16 for copper and aluminum conductors, with standard derating factors for temperature and conduit fill.
| Wire Size | Cu 60°C (TW,UF) |
Cu 75°C (THW,THWN) |
Cu 90°C (THHN,XHHW-2) |
Al 60°C (TW,UF) |
Al 75°C (THW,THWN) |
Al 90°C (THHN,XHHW-2) |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | — | — |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 30 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 60 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 190 | 230 | 255 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
| 600 kcmil | 355 | 420 | 475 | 285 | 340 | 385 |
| 750 kcmil | 400 | 475 | 535 | 320 | 385 | 435 |
| 1000 kcmil | 455 | 545 | 615 | 375 | 445 | 500 |
AMBIENT TEMPERATURE CORRECTION — NEC 310.15(B)(1)
| Ambient Temp (°F) | 60°C Factor | 75°C Factor | 90°C Factor |
|---|---|---|---|
| 70-77 | 1.08 | 1.04 | 1.04 |
| 78-86 | 1 | 1 | 1 |
| 87-95 | 0.91 | 0.96 | 0.96 |
| 96-104 | 0.82 | 0.91 | 0.91 |
| 105-113 | 0.71 | 0.87 | 0.87 |
| 114-122 | 0.58 | 0.82 | 0.82 |
| 123-131 | 0.41 | 0.76 | 0.76 |
| 132-140 | — | 0.71 | 0.71 |
| CONDUIT FILL ADJUSTMENT — NEC 310.15(C)(1) | |||
| Number of Current-Carrying Conductors | Adjustment Factor | ||
| 4-6 | 0.8 | ||
| 7-9 | 0.7 | ||
| 10-20 | 0.5 | ||
| 21-30 | 0.45 | ||
| 31-40 | 0.4 | ||
| 41+ | 0.35 | ||
| DERATING CALCULATOR | |||
| Base ampacity (from Table 310.16) | 100 | A | |
| Ambient temp correction factor | 0.91 | — | |
| Conduit fill adjustment factor | 0.8 | — | |
| Derated ampacity | A |
Source: NEC_Cable_Ampacity_Reference_v1.xlsx
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.