Inflection Point Engineering Reference Tables

NEC Cable Ampacity

Allowable ampacities per NEC Table 310.16 for copper and aluminum conductors, with standard derating factors for temperature and conduit fill.

Table 310 16

Wire Size Cu 60°C
(TW,UF)
Cu 75°C
(THW,THWN)
Cu 90°C
(THHN,XHHW-2)
Al 60°C
(TW,UF)
Al 75°C
(THW,THWN)
Al 90°C
(THHN,XHHW-2)
14 AWG 15 20 25
12 AWG 20 25 30 15 20 25
10 AWG 30 35 40 25 30 35
8 AWG 40 50 55 30 40 45
6 AWG 55 65 75 40 50 60
4 AWG 70 85 95 55 65 75
3 AWG 85 100 115 65 75 85
2 AWG 95 115 130 75 90 100
1 AWG 110 130 145 85 100 115
1/0 125 150 170 100 120 135
2/0 145 175 195 115 135 150
3/0 165 200 225 130 155 175
4/0 195 230 260 150 180 205
250 kcmil 215 255 290 170 205 230
300 kcmil 240 285 320 190 230 255
350 kcmil 260 310 350 210 250 280
400 kcmil 280 335 380 225 270 305
500 kcmil 320 380 430 260 310 350
600 kcmil 355 420 475 285 340 385
750 kcmil 400 475 535 320 385 435
1000 kcmil 455 545 615 375 445 500

Derating

AMBIENT TEMPERATURE CORRECTION — NEC 310.15(B)(1)

Ambient Temp (°F) 60°C Factor 75°C Factor 90°C Factor
70-77 1.08 1.04 1.04
78-86 1 1 1
87-95 0.91 0.96 0.96
96-104 0.82 0.91 0.91
105-113 0.71 0.87 0.87
114-122 0.58 0.82 0.82
123-131 0.41 0.76 0.76
132-140 0.71 0.71
CONDUIT FILL ADJUSTMENT — NEC 310.15(C)(1)
Number of Current-Carrying Conductors Adjustment Factor
4-6 0.8
7-9 0.7
10-20 0.5
21-30 0.45
31-40 0.4
41+ 0.35
DERATING CALCULATOR
Base ampacity (from Table 310.16) 100 A
Ambient temp correction factor 0.91
Conduit fill adjustment factor 0.8
Derated ampacity A

Source: NEC_Cable_Ampacity_Reference_v1.xlsx