Reference Tables
Process control signal types — 4–20 mA HART, FOUNDATION Fieldbus, PROFIBUS, Modbus, OPC UA — with typical applications.
Analog Signal Standards
| Signal | Range | Physical | Wiring | Max distance | Typical use | Notes |
|---|---|---|---|---|---|---|
| 4-20 mA DC | 4=LRV, 20=URV | Two-wire current loop | 2-wire shielded TP | ~3000 ft | Process transmitters (pressure, flow, level, temp) | De-facto standard; NE43 fail-low <3.6 or fail-high >21 mA diagnostic. |
| 0-10 V DC | LRV-URV | Single-ended voltage | 2-wire TP | <50 ft | Analyzer outputs, VFD speed reference | Ground-loop prone; use isolators on long runs. |
| +/-10 V DC | +/-FS | Bipolar | 2-wire TP | <50 ft | Servo drive command, bipolar measurements | Same constraints as 0-10 V. |
| 1-5 V DC | 1=LRV, 5=URV | From 250 ohm sense R | Branched from 4-20 mA | Same as 4-20 mA | Legacy DCS AI; still common on Honeywell | Formed across a 250 ohm dropping resistor. |
| Pt100 / Pt1000 RTD | Resistance | 100 or 1000 ohm @ 0C | 3- or 4-wire | <200 ft typ. | Temperature | 3-wire cancels lead resistance; 4-wire most accurate. |
| Thermocouple (K, J, T, N) | mV vs Cold Junction | Seebeck EMF | Compensating TC extension cable | <100 ft, more w/ transmitter | High T measurement | Always need cold-junction compensation at DCS/transmitter. |
| Frequency (pulse) | 0-10 kHz typ | Square-wave or sine | Shielded 2-wire | <2000 ft | Turbine/mag flow totalizer | Scale to engineering units in DCS or flow computer. |
| Namur sensor (IEC 60947-5-6) | <1.2 mA off, >2.1 mA on | 2-wire proximity | Shielded 2-wire | <330 ft | IS proximity / limit switches | Loop powered by IS barrier; used in Zone 0/1. |
| 3-15 psi pneumatic | 3=LRV, 15=URV | Instrument-air signal | 6x1 mm or 1/4 in PE tubing | <300 ft | Legacy controllers & valve positioners | Rarely designed new; mostly retrofit applications. |
Digital / Fieldbus / Industrial Ethernet Comparison
| Protocol | Layer | Speed | Topology | Max distance (copper) | Devices/segment | Power on bus | Typical use |
|---|---|---|---|---|---|---|---|
| HART 7 | Superimposed on 4-20 mA | 1.2 kbps | Point-to-point / multidrop | Same as 4-20 mA loop | 1 (P-to-P) or 15 (MD) | No (host powers loop) | Legacy w/ smart device access; diagnostics, cal data |
| FOUNDATION Fieldbus H1 | IEC 61158-2 | 31.25 kbps | Bus / tree (trunk+spur) | 1900 m trunk | 16 (non-IS) / 6-12 (IS) | Yes (9-32 VDC) | Plant-wide control w/ device-resident function blocks |
| PROFIBUS-PA | IEC 61158-2 | 31.25 kbps | Bus / tree | 1900 m | 32 non-IS / 6-12 IS | Yes | Process automation w/ PROFIBUS-DP backbone |
| PROFIBUS-DP | RS-485 | 9.6 kbps - 12 Mbps | Bus | 100-1200 m (rate dep.) | 126 via repeaters | No | Factory automation, drives, I/O |
| Modbus RTU | RS-485 | 9.6-115.2 kbps | Bus | 4000 ft | 247 | No | VFDs, power meters, simple devices |
| Modbus TCP | Ethernet/TCP | 10/100/1000 Mbps | Star | 100 m/seg | IP-limited | No | PLC to PLC, OPC gateways |
| EtherNet/IP | ODVA / CIP | 10/100/1000 Mbps | Star / ring (DLR) | 100 m/seg | IP-limited | PoE option | Rockwell control, drives, motion |
| PROFINET | PI / IEEE 802 | 100/1000 Mbps | Star / line | 100 m/seg | IP-limited | PoE option | Siemens control, drives; RT/IRT real-time |
| EtherCAT | ETG | 100 Mbps | Line / ring | 100 m/seg | 65535 | No | High-speed motion, servo |
| OPC UA | IEC 62541 | Ethernet-dep | Any IP | Any | Any | No | MES/ERP integration, IT/OT bridge |
NAMUR NE 43 (4-20 mA Failure) and NE 107 (Diagnostic Categories)
| Band (mA) | NE 43 State | Meaning | Typical use |
|---|---|---|---|
| < 3.6 | Fault (low) | Transmitter failure, sensor open | Shutdown diagnostic; alarm low |
| 3.6 - 3.8 | Saturation low | Under-range | Out-of-range indication |
| 3.8 - 4.0 | Live zero margin | Just below 4 mA; valid zero | Normal |
| 4.0 - 20.0 | Valid | Normal measurement range | Process signal |
| 20.0 - 20.5 | Live full margin | Just above 20 mA | Normal |
| 20.5 - 21.0 | Saturation high | Over-range | Out-of-range indication |
| > 21.0 | Fault (high) | Transmitter failure | Shutdown diagnostic; alarm high |
| NAMUR NE 107 Diagnostic Categories | |||
| Failure (F) | Output signal is invalid due to malfunction in the device or its periphery. | ||
| Function check (C) | Output signal temporarily invalid (test, local operation, frozen). | ||
| Out-of-specification (S) | Deviations from ambient or process conditions outside spec; info only. | ||
| Maintenance required (M) | Device operates OK but remaining service buffer is limited; schedule maintenance. |
Source: Instrumentation_Signal_Standards_Reference_v1.xlsx
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.