Instrumentation Signal Standards

Process control signal types — 4–20 mA HART, FOUNDATION Fieldbus, PROFIBUS, Modbus, OPC UA — with typical applications.

README

Analog Signals

Analog Signal Standards

Signal Range Physical Wiring Max distance Typical use Notes
4-20 mA DC 4=LRV, 20=URV Two-wire current loop 2-wire shielded TP ~3000 ft Process transmitters (pressure, flow, level, temp) De-facto standard; NE43 fail-low <3.6 or fail-high >21 mA diagnostic.
0-10 V DC LRV-URV Single-ended voltage 2-wire TP <50 ft Analyzer outputs, VFD speed reference Ground-loop prone; use isolators on long runs.
+/-10 V DC +/-FS Bipolar 2-wire TP <50 ft Servo drive command, bipolar measurements Same constraints as 0-10 V.
1-5 V DC 1=LRV, 5=URV From 250 ohm sense R Branched from 4-20 mA Same as 4-20 mA Legacy DCS AI; still common on Honeywell Formed across a 250 ohm dropping resistor.
Pt100 / Pt1000 RTD Resistance 100 or 1000 ohm @ 0C 3- or 4-wire <200 ft typ. Temperature 3-wire cancels lead resistance; 4-wire most accurate.
Thermocouple (K, J, T, N) mV vs Cold Junction Seebeck EMF Compensating TC extension cable <100 ft, more w/ transmitter High T measurement Always need cold-junction compensation at DCS/transmitter.
Frequency (pulse) 0-10 kHz typ Square-wave or sine Shielded 2-wire <2000 ft Turbine/mag flow totalizer Scale to engineering units in DCS or flow computer.
Namur sensor (IEC 60947-5-6) <1.2 mA off, >2.1 mA on 2-wire proximity Shielded 2-wire <330 ft IS proximity / limit switches Loop powered by IS barrier; used in Zone 0/1.
3-15 psi pneumatic 3=LRV, 15=URV Instrument-air signal 6x1 mm or 1/4 in PE tubing <300 ft Legacy controllers & valve positioners Rarely designed new; mostly retrofit applications.

Digital Fieldbus

Digital / Fieldbus / Industrial Ethernet Comparison

Protocol Layer Speed Topology Max distance (copper) Devices/segment Power on bus Typical use
HART 7 Superimposed on 4-20 mA 1.2 kbps Point-to-point / multidrop Same as 4-20 mA loop 1 (P-to-P) or 15 (MD) No (host powers loop) Legacy w/ smart device access; diagnostics, cal data
FOUNDATION Fieldbus H1 IEC 61158-2 31.25 kbps Bus / tree (trunk+spur) 1900 m trunk 16 (non-IS) / 6-12 (IS) Yes (9-32 VDC) Plant-wide control w/ device-resident function blocks
PROFIBUS-PA IEC 61158-2 31.25 kbps Bus / tree 1900 m 32 non-IS / 6-12 IS Yes Process automation w/ PROFIBUS-DP backbone
PROFIBUS-DP RS-485 9.6 kbps - 12 Mbps Bus 100-1200 m (rate dep.) 126 via repeaters No Factory automation, drives, I/O
Modbus RTU RS-485 9.6-115.2 kbps Bus 4000 ft 247 No VFDs, power meters, simple devices
Modbus TCP Ethernet/TCP 10/100/1000 Mbps Star 100 m/seg IP-limited No PLC to PLC, OPC gateways
EtherNet/IP ODVA / CIP 10/100/1000 Mbps Star / ring (DLR) 100 m/seg IP-limited PoE option Rockwell control, drives, motion
PROFINET PI / IEEE 802 100/1000 Mbps Star / line 100 m/seg IP-limited PoE option Siemens control, drives; RT/IRT real-time
EtherCAT ETG 100 Mbps Line / ring 100 m/seg 65535 No High-speed motion, servo
OPC UA IEC 62541 Ethernet-dep Any IP Any Any No MES/ERP integration, IT/OT bridge

NAMUR NE43 107

NAMUR NE 43 (4-20 mA Failure) and NE 107 (Diagnostic Categories)

Band (mA) NE 43 State Meaning Typical use
< 3.6 Fault (low) Transmitter failure, sensor open Shutdown diagnostic; alarm low
3.6 - 3.8 Saturation low Under-range Out-of-range indication
3.8 - 4.0 Live zero margin Just below 4 mA; valid zero Normal
4.0 - 20.0 Valid Normal measurement range Process signal
20.0 - 20.5 Live full margin Just above 20 mA Normal
20.5 - 21.0 Saturation high Over-range Out-of-range indication
> 21.0 Fault (high) Transmitter failure Shutdown diagnostic; alarm high
NAMUR NE 107 Diagnostic Categories
Failure (F) Output signal is invalid due to malfunction in the device or its periphery.
Function check (C) Output signal temporarily invalid (test, local operation, frozen).
Out-of-specification (S) Deviations from ambient or process conditions outside spec; info only.
Maintenance required (M) Device operates OK but remaining service buffer is limited; schedule maintenance.

Source: Instrumentation_Signal_Standards_Reference_v1.xlsx