Reference Tables
Gas groups, temperature classes, zone definitions, and equipment protection level (EPL) mapping per IEC 60079 series.
| IEC Zone | NEC/CEC Equivalent | Definition (IEC 60079-10-1) | Typical Example | Reference |
|---|---|---|---|---|
| Zone 0 | Class I Div 1 (continuous) | Explosive gas atmosphere is present continuously or for long periods | Inside fuel tank vapor space | IEC 60079-10-1:2020 Sec 6 |
| Zone 1 | Class I Div 1 (intermittent) | Explosive gas atmosphere is likely to occur in normal operation occasionally | Around vents, sample points, pump seals | IEC 60079-10-1:2020 Sec 6 |
| Zone 2 | Class I Div 2 | Explosive gas atmosphere is not likely to occur in normal operation; if it does, only briefly | General process areas with closed equipment | IEC 60079-10-1:2020 Sec 6 |
| Zone 20 | Class II Div 1 (continuous) | Combustible dust is present continuously or for long periods | Interior of dust collector, hopper | IEC 60079-10-2:2015 |
| Zone 21 | Class II Div 1 (intermittent) | Combustible dust is likely to occur in normal operation occasionally | Adjacent to dust filter charge points | IEC 60079-10-2:2015 |
| Zone 22 | Class II Div 2 | Combustible dust is not likely to occur in normal operation | General areas around dust-handling equipment | IEC 60079-10-2:2015 |
| IEC Group | NEC Group | Representative Gas | MESG (mm) | MIC Ratio | Reference |
|---|---|---|---|---|---|
| IIA | D | Methane / Propane | >0.90 | >0.80 | IEC 60079-20-1:2017 |
| IIB | C | Ethylene | 0.50-0.90 | 0.45-0.80 | IEC 60079-20-1:2017 |
| IIB+H2 | C+H2 | Hydrogen-mix special | as IIB | as IIB | IEC 60079-20-1:2017 |
| IIC | A/B | Hydrogen / Acetylene | <0.50 | <0.45 | IEC 60079-20-1:2017 |
| I | MSHA | Methane (mining) | for mining apps | - | IEC 60079-0:2017 |
| IIIA | E (fibers) | Combustible flyings | - | - | IEC 60079-0:2017 |
| IIIB | F (dust) | Non-conductive dust | - | - | IEC 60079-0:2017 |
| IIIC | G (dust) | Conductive dust | - | - | IEC 60079-0:2017 |
| T-Class | Max Surface Temp deg C | Max Surface Temp deg F | Note | Reference |
|---|---|---|---|---|
| T1 | 450 | 842 | Most flexible; covers most hydrocarbons | IEC 60079-0:2017 |
| T2 | 300 | 572 | Below H2 AIT; many service fluids | IEC 60079-0:2017 |
| T3 | 200 | 392 | Below diesel AIT (~210C) | IEC 60079-0:2017 |
| T4 | 135 | 275 | Below H2S AIT (~270C); below ether AIT | IEC 60079-0:2017 |
| T5 | 100 | 212 | Specialty - low-AIT solvents | IEC 60079-0:2017 |
| T6 | 85 | 185 | CS2 / very low AIT services | IEC 60079-0:2017 |
| Code | Method Name | IEC Standard | Permissible Zones | Description |
|---|---|---|---|---|
| Ex d | Flameproof enclosure | IEC 60079-1 | 1, 2 | Contains internal explosion; flame-resistant joints |
| Ex e | Increased safety | IEC 60079-7 | 1, 2 | No arcing/sparking parts; higher creepage and clearance |
| Ex i | Intrinsic safety | IEC 60079-11 | 0 (ia), 1 (ib), 2 (ic) | Energy/temperature limited; safest for instruments |
| Ex p | Pressurized enclosure | IEC 60079-2 | 1 (px), 2 (py/pz) | Inert gas purge maintains positive pressure |
| Ex m | Encapsulation | IEC 60079-18 | 0 (ma), 1 (mb), 2 (mc) | Components encased in compound |
| Ex n | Non-incendive | IEC 60079-15 | 2 | Non-sparking, restricted breathing |
| Ex o | Oil immersion | IEC 60079-6 | 2 | Components submerged in oil |
| Ex q | Powder filling | IEC 60079-5 | 2 | Sand-filled enclosure |
| Ex t | Dust ignition protection | IEC 60079-31 | 20 (ta), 21 (tb), 22 (tc) | Dust-tight enclosure with limited surface temp |
| Ex op | Optical radiation | IEC 60079-28 | 0 (op is), 1 (op pr), 2 (op sh) | Inherently safe / protected / shielded optical |
Source: IEC_60079_Hazardous_Area_Codes_v1.xlsx
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.