Inflection Point Engineering Section 15 — Inspection

Eddy Current Examination

IPE Engineering Practice IPE-EP-15-2-2

Document number: IPE-EP-15-2-2 · Section: 15 — Inspection

1.0

1.1

1.2

1.3

1.4

1.5

2.0

SCOPE

This practice covers the minimum requirements to perform all methods of eddy current tube testing, magnetic flux leakage, and IRIS tube testing by contractors working on equipment belonging to Inflection Point Engineering, LLC. These methods are used for volumetric examination of installed heat exchanger and airfin tubes for detection of I.D. and O.D. discontinuities.

(*) Inspection contractors selected to bid on Inflection Point Engineering, LLC work shall submit their procedures for review and approval by the responsible Inflection Point Engineering, LLC Inspection Authority during the bidding process.

Inspection contractors who have had their procedures approved may perform inspections in accordance with the approved procedures.

Any deviation to this practice shall be approved by the procedure described in EP 1–1–3.

An asterisk (*) indicates that a decision by the Owner’s Level III or Inspection Authority is required or that additional information may be included by the purchaser.

REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices
ASME Codes
Sec. V Nondestructive Testing - ARTICLE 8
ASNT Codes
TC-1A RP for Personnel Qualification and Certification in Nondestructive Testing

DEFINITIONS

DESCRIPTION OF TEST METHODS

0.02 inch deep. This technique is typically very slow and requires very clean tube I.D.’s.

RESPONSIBILITIES

CERTIFICATION OF PERSONNEL

SAFETY

PREPARATIONS BEFORE INSPECTION

9.0

9.1

9.2

9.3

9.4

9.5

9.6

9.7

9.8

9.9

Electrical connections, air, and water shall be provided at the work site by Inflection Point Engineering, LLC or their maintenance contractors as needed.

The inside diameters of tubes shall be cleaned before testing as needed to assure reliable test results. Cleaning shall be done by Inflection Point Engineering, LLC or their maintenance contractors.

Tubes shall typically be cleaned by high pressure water washing, but in some cases mechanical cleaning may be needed to prepare the tube ID’s for examination.

(*) Personnel conducting tube examinations shall report any problems encountered with dirty tubes to the responsible Inflection Point Engineering, LLC Inspector. The inspector shall decide if additional cleaning is required.

EXAMINATION REQUIREMENTS & CALIBRATION OF TEST EQUIPMENT

All examinations shall be performed in accordance with a written procedure that contains sufficient detail to insure equipment is operated in accordance with the instrument manufacturer’s operating instructions.

The contractor shall be equipped with appropriate calibration standards for the tube size and metallurgy to be examined.

The calibration tube shall contain artificial or natural discontinuities that adequately simulate the discontinuities expected during the examination. Artificial discontinuities may be in the form of flat bottom holes, grooves, wall reductions, or other suitable simulations. Each standard shall be properly identified.

A copy of the strip chart or computer print out of the calibration conducted immediately prior to the examination, and for each calibration check conducted during the examination procedure, shall be included with test documentation. Calibration confirmation shall be performed every 4 hours, when equipment has been idle for more than one hour, after a power loss, if any of the test system equipment is changed, or if calibration is in doubt. If at any check the equipment is found to be out of calibration, the system shall be recalibrated, and the tubes examined since the last calibration shall be reexamined in reverse order until it is determined that the examinations are valid. If needed all tubes since the last calibration shall be reexamined.

After completion of the examination a calibration check shall be conducted. The strip chart or computer print out of this calibration check shall also be included with the test documentation.

Calibrations shall be performed by pulling probes through the tube standards at the speed to be used during the inspection.

Each defect indicated on the strip chart or computer print out of the calibration shall be marked by hand on the chart or print out indicating what the defect is.

Test standards shall be manufactured in accordance with the contractors written procedures, and ASME Sec V, Article 8, Appendix I.

Equipment and materials used to conduct tube examinations for Inflection Point Engineering, LLC facilities shall have adequate ranges and accuracy and shall be calibrated or certified as required by the contractors written procedures and applicable codes.

EXAMINATION

EVALUATION OF INDICATIONS

REPORTING OF INSPECTION RESULTS

inspector a preliminary examination report with a summary of all tubes examined.