Inflection Point Engineering Section 13 — Electrical

Medium Voltage Vacuum Switchgear

IPE Engineering Practice IPE-EP-13-5-2

Document number: IPE-EP-13-5-2 · Section: 13 — Electrical

1.0

1.1

1.2

1.3

1.4

2.0

SCOPE

This Practice, including the Medium Voltage Vacuum Switchgear Data Sheet (EP 13–5–2DS), covers the minimum requirements for assemblies of medium voltage, indoor and outdoor, walk– in sheltered maintenance aisle, and non walk–in outdoor type switchgear with ratings of 5KV, 15KV or 35KV, 3 phase, 3 wire, 60 hertz, for operation on either ungrounded, low resistance or solidly grounded systems as specified on the Data Sheet. Switchgear shall conform to this Practice, unless written approval is obtained from the Owner for exceptions.

This Practice is appropriate for attachment to an inquiry or purchase document when accompanied by the referenced IPE Engineering Practices and completed Data Sheets.

Any deviation from this Practice must be approved by the procedure described in EP 1–1–3. A revision bar indicates all changes made to this Revision.

REFERENCES

All applicable sections of the latest standards and codes listed below are a part of this Practice unless amended herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices
EP 13–5–2DS Medium Voltage Vacuum Switchgear Data Sheet EP 13–6–1 Medium Voltage Motor Controllers
EP 13–24–1 Electrical Bus Duct 480 Volt and Higher
EP 13–24–1DS Electrical Bus Duct 480 Volt and Higher Data Sheet
ANSI Standards
C37 Complete Edition–Circuit Breakers, Switchgear, Relays, Substations and Fuses C37.2 Electrical Power System Device Function Numbers
C37.11 Electrical Control for AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis or a Total Current Basis (Withdrawn)
C57.12.50 Requirements for Ventilated Dry Type Distribution Transformers C57.13 Requirements for Instrument Transformers
C57.13.1 Guide for Testing Relaying Current Transformers
C57.12.91 Test Code for Dry Type Distribution and Power Transformers
ANSI/IEEE
C37.010 Application Guide for AC High Voltage Circuit Breakers Rated on a Symmetrical
Current Basis
NFPA
70 National Electrical Code

3.0

3.1

3.2

3.3

3.4

3.5

3.6

4.0

5.0

5.1

5.1.1

DEFINITIONS

Contractor – Company or business that agrees to furnish materials or perform specified services at a specified price and/or rate to the Owner.

Inspector – A Inflection Point Engineering, LLC appointed engineer or inspector.

Manufacturer – The recipient of a direct or indirect purchase order for materials and/or equipment. In this context, a direct order is one issued to a Manufacturer by a Contractor or the Owner. An indirect order is one issued to a Manufacturer by a vendor (recipient of a direct order) for materials, fabricated components, or subassemblies.

Owner – Inflection Point Engineering, LLC.

Owner’s Engineer – A Inflection Point Engineering, LLC appointed engineer.

Purchaser – The party placing a direct purchase order. The Purchaser is the Owner’s designated representative.

SERVICE CONDITIONS

Medium voltage switchgear assemblies shall perform satisfactorily when operated indoors or outdoor in a walk–in, sheltered maintenance aisle housing, or outdoor non–walk–in enclosure, either intermittently or continuously in an atmosphere typical of petroleum plants. Unless otherwise noted on the Medium Voltage Switchgear Data Sheet, the switchgear assemblies shall be for use in a 104ºF maximum ambient, –22ºF minimum ambient, and at an altitude of 3300 feet or lower.

DESIGN, CONSTRUCTION AND MATERIALS

Basic Construction

Enclosures

WARNING

OPENING DRAWER (OR DOOR) TRIPS MOTOR

WARNING

OPENING DRAWER (OR DOOR) MAY INITIATE A DEAD BUS TRANSFER AND/OR

DE-ENERGIZE A BUS SECTION.

WARNING

OPERATION OF THIS RELAY TRIPS MORE THAN ONE CIRCUIT BREAKER AS LISTED: BREAKER

BREAKER etc.

34.5 KV, green for 4.16 KV, white for 2.4 KV, and orange for 480V.

TESTING AND INSPECTION

57.13.1. The ratio shall be verified per the voltage or current method. The polarity shall be determined by the AC voltage test method. The DC voltage test method shall not be used to verify CT polarity.

When witness testing is specified, the Owner shall witness the complete testing of all items outlined in Section 6.1 of this Practice.

DRAWINGS AND DATA REQUIREMENTS

All drawings provided for this equipment shall show equipment as specified and ordered. Typical drawings are not acceptable unless they are revised to show only the equipment being furnished. Drawings shall be supplied in the quantities and format shown on the Data Sheets.

SPARE PARTS

A complete spare parts recommendation based on the total purchase order is required within 60 days after the Manufacturer receives the purchase order. Spare parts recommendations shall include:

SHIPPING

10.0 TABLES

TABLE 1 DOCUMENTATION REQUIREMENTS

FOR CERTIFIED INFORMATION REQUIRED IN ELECTRONIC FORMAT per EP 13–5–2

Item Description Format As–Built
1 Complete structural drawings including but not limited to those items in paragraph 7.2.1. See EP 2-5-2 Yes
2 Three line diagrams per paragraph 7.2.2. See EP 2-5-2 Yes
3 Certified elementary diagrams for all equipment provided per paragraph 7.2.3. See EP 2-5-2 Yes
4 Listing of all nameplates provided including location identification. See EP 2-5-2 Yes
5 Copies of all test reports to include requirements of Section 6.0 and those test included in the purchase documents. See EP 2-5-2 Yes
6 Complete certified installation, operating and maintenance manuals for all equipment/items provided, paragraph 7.3.2. See EP 2-5-2 Yes