Inflection Point Engineering Section 13 — Electrical

Low Voltage Switchgear

IPE Engineering Practice IPE-EP-13-5-1

Document number: IPE-EP-13-5-1 · Section: 13 — Electrical

1.0

1.1

1.2

1.3

1.4

2.0

SCOPE

This Practice, including the Low Voltage Switchgear Data Sheets (EP 13–5–1DS), covers the minimum requirements for assemblies of low voltage, indoor and outdoor, walk–in sheltered maintenance aisle, and non walk–in outdoor type switchgear with ratings of 600 volts, 3 phase, 3 wire, 60 hertz, for operation on resistance grounded and solidly grounded systems.

This Practice is appropriate for attachment to an inquiry or purchase document when accompanied by the referenced IPE Engineering Practices and completed data sheets.

Any deviation from this Practice must be approved by the procedure in EP 1–1–3. A revision bar indicates all changes made to this Revision.

REFERENCES

All applicable sections of the latest standards and publications listed below are a part of this Practice unless amended herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices EP 13–5–1DS Low Voltage Switchgear Data Sheet
EP 13–6–2 Motor Control Centers 600 Volt Class EP 13–10–1 Neutral Grounding Resistor
EP 13–10–1DS Neutral Grounding Resistor Data Sheet
EP 13–24–1 Electrical Bus Duct 480 Volt and Higher
ANSI
C37.2 Electrical Power System Device Function Numbers
C37.11 Electrical Control for AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis or a Total Current Basis (Withdrawn)
C37.13 Low Voltage AC Power Circuit Breakers Used in Enclosures C37.14 Low Voltage DC Power Circuit Breakers Used in Enclosures
C37.16 Preferred Ratings, Related Requirements, and Application Recommendation for Low Voltage Power Circuit Breakers and AC Power Circuit Protectors
C37.17 Trip Devices for AC and General Purpose DC Low–Voltage Power Circuit Breakers C37.20.1 Standard For Metal–Enclosed Low–Voltage Power Circuit Breaker Switchgear C37.23 Guide For Metal–Enclosed bus and Calculating Losses in Isolated–Phase Bus C37.50 Test Procedures for Low–Voltage AC Power Circuit Breakers Used in Enclosures C37.51 Conformance Testing of Metal–Enclosed Low–Voltage AC Power Circuit Breakers
Switchgear Assemblies

STANDARDS AND PUBLICATIONS (CONT.)

ANSI (Continued)
C37.90 Relays and Relay Systems Associated with Electric Power Apparatus
C57.13 Requirements for Instrument Transformers
NEMA
SG–3 Low–Voltage Power Circuit Breakers
SG–5 Power Switchgear Assemblies
NFPA
70 National Electrical Code
U.L.
Metal Enclosed Low–Voltage Power Circuit Breaker Switchgear

3.0

3.1

3.2

3.3

3.4

3.5

3.6

4.0

5.0

5.1

5.1.1

DEFINITIONS

Contractor – Company or business that agrees to furnish materials or perform specified services at a specified price and/or rate to the Owner.

Inspector –- A Inflection Point Engineering, LLC appointed engineer or inspector.

Manufacturer –- The recipient of a direct or indirect purchase order for materials and/or equipment. In this context, a direct order is one issued to a Manufacturer by a Contractor or the Owner. An indirect order is one issued to a Manufacturer by a vendor (recipient of a direct order) for materials, fabricated components, or subassemblies.

Owner – Inflection Point Engineering, LLC.

Owner’s Engineer – A Inflection Point Engineering, LLC appointed engineer.

Purchaser – The party placing a direct purchase order. The Purchaser is the Owner’s designated representative.

SERVICE CONDITIONS

Low voltage switchgear shall perform satisfactorily when operated indoors or outdoors in a walk–in, sheltered maintenance aisle housing, or outdoor non walk–in enclosure either intermittently or continuously in an atmosphere typical of petrochemical plants. The switchgear shall be designed for use in the 104F maximum ambient, –22F minimum ambient, and at an altitude of 3300 feet or lower.

DESIGN CONSTRUCTION AND MATERIALS

Basic Construction

Enclosures

D.C. control.

D.C. control.

TESTING AND INSPECTION

6.2 Witness Testing

When witness testing is specified, the Owner shall witness the complete testing of all items outlined in Section 6.1.

DRAWINGS AND DATA REQUIREMENTS

All drawings provided for this equipment shall show equipment as specified and ordered. Typical drawings are not acceptable unless they are revised to show only the equipment being furnished. Drawings shall be supplied in the quantities shown on the Data Sheets.

SPARE PARTS

A complete spare parts recommendation based on the total purchase order is required within 60 days after the Manufacturer receives the purchase order. Spare parts recommendations shall include:

SHIPPING

10.0 TABLES

TABLE 1

CERTIFIED INFORMATION REQUIRED IN ELECTRONIC FORMAT FOR ELECTRICAL PER EP 13–5–1

Item Description Format As–Built
1 Complete certified structural drawings including but not limited to those items in paragraph 7.2.1 See EP 2-5-2 Yes
2 Certified three line diagrams per paragraph 7.2.2 See EP 2-5-2 Yes
3 Certified elementary diagrams for all equipment provided per paragraph 7.2.3 See EP 2-5-2 Yes
4 Certified detailed connection (wiring) diagrams per paragraph 7.2.4 See EP 2-5-2 Yes
5 Certified listing of all nameplates provided including location identification See EP 2-5-2 Yes
6 Certified copies of all test reports to include requirements of Section 6.0 and those tests included in the purchase documents See EP 2-5-2 Yes
7 Complete certified installation, operating and maintenance manuals for all equipment/items provided, paragraph 7.3.2 See EP 2-5-2 Yes