Inflection Point Engineering Section 13 — Electrical

Power Transformers

IPE Engineering Practice IPE-EP-13-4-1

Document number: IPE-EP-13-4-1 · Section: 13 — Electrical

Table 2 Bil Requirements For Low Voltage Ratings 21Table 2 Bil Requirements For Low Voltage Ratings 21

Table 3 Minimum Fan Cooled Ratings 22Table 3 Minimum Fan Cooled Ratings 22

Table 4 CT Accuracy Class Requirements 22Table 4 CT Accuracy Class Requirements 22

Table 5 Documentation Requirements For Power Transformers per EP 13–4–1 23Table 5 Documentation Requirements For Power Transformers per EP 13–4–1 23

SCOPE

2.0 REFERENCES

All applicable sections of the latest standards and codes listed below are a part of this Practice for construction, wiring and testing unless amended herein. It shall be the Manufacturer’s and or suppliers responsibility to be or become knowledgeable to the requirements of these standards and codes. Any changes or alterations to the equipment to make it meet the requirements of the referenced standards and codes shall be at the expense of the Manufacturer and/or the supplier.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices EP 13–4–1 DS Power Transformers Data Sheet
EP 13–25–1 Medium Voltage Metal Enclosed Switches (ME Switches)
EP 13–25–1 DS Medium Voltage Metal Enclosed Switches (ME Switches)
ANSI Standards
C57 Complete Edition; Distribution Power and Regulating Transformers
C76.1 General Requirements and Test Procedure for Outdoor Apparatus Bushings
OSHA Standard
OSHA Standard 1910.212
NFPA Standard
70 National Electrical Code

STANDARDS AND PUBLICATIONS (Cont.)

NEMA Standard
TR–1 Transformers, Regulators and Reactors
National Bureau of Standard
NBS Technical Note 1204 Calibration of Test Systems for Measuring Power Losses of
Transformers

DEFINITIONS

4.0 SERVICE CONDITIONS

Transformers shall perform satisfactorily when operated outdoors, either intermittently or continuously, in a corrosive atmosphere likely to be encountered in petroleum and chemical plant installations. Unless otherwise noted on the Transformer Data Sheet, transformers shall be for use in a 104F maximum, –15F minimum ambient at an altitude of 3,300 feet or lower and installed on a level concrete pad.

DESIGN CONSTRUCTION AND MATERIALS

All transformers covered by this Practice shall be designed and nameplated for a 55/65C average winding temperature rise by resistance and suitable for continuous operation with 65C average winding temperature rise by resistance and 80C hottest–spot winding temperature.

Transformers covered by this Practice shall be capable of meeting the short circuit requirements of ANSI C57.12.00 and C57.12.90. The design offered shall have been tested and successfully met the ANSI short circuit requirements.

Sound levels shall not exceed the values given in NEMA Standard TR–1 and/or levels required by OSHA.

0.125 inch thickness metal, as specified on the Data Sheet, and have a center spacing between panels of no less than 4 inches.

The transformer assembly including tank, radiators, throats, and terminal chambers shall be cleaned to the bare metal and sealed with a moisture resistant, long–life coating. The coating shall consist of rust inhibiting primer, Manufacturer’s standard intermediate coating and two finish coats of light gray catalyzed epoxy. The total coating thickness shall be a minimum of 5 mils. If the Manufacturer’s paint system is different, request that complete details of the system be provided to the Owner for review and approval. The details shall include specific justification of the paint system for use in a petro–chemical environment.

When current transformers are specified on the Transformer Data Sheet, they shall be in accordance with the following:

Each transformer shall be equipped with all standard ANSI accessories and shall include, but not be limited to the following:

When lightning arresters are specified on the Transformer Data Sheet they shall comply with the following:

If liquid filling of any part of the transformer is required at job site, the transformer Manufacturer shall furnish the liquid, job site supervision, and furnish or make available a suitable filter press and vacuum pump. The transformer Manufacturer shall also test the transformer oil after job site filling with test to include those items identified in paragraph 5.23.2. The oil testing shall be included in the field service cost.

5.25 Storage

Any items requiring special storage at the job site shall be appropriately labeled as such, easily unpacked (accessible) and accompanied with appropriate storage and installation instructions.

TESTING

A report of transformer tests shall be submitted for each transformer. The tests shall be performed in accordance with the ANSI Standard Test Code C57.12.90. The following changes and/or requirements for testing in addition to those in ANSI C57.12.90 shall apply:

6.1.4.1 of this Practice).

DRAWING AND DATA REQUIREMENTS

All drawings provided for this equipment shall show equipment as specified and ordered. Typical drawings are not acceptable unless they are revised to show only the equipment being furnished. Drawings shall be supplied in the quantities shown on the Transformer Data Sheet.

SPARE PARTS

A complete spare parts recommendation based on the total purchase order is required within 60 days after the Manufacturer (Supplier) receives the purchase order. Spare parts recommendations shall include:

SHIPPING

10.0 TABLES

TABLE 1

TRANSFORMER BIL REQUIRED FOR THE VOLTAGE CLASS INDICATED REGARDLESS OF WINDING LOCATION

Voltage Class (KV) Substation Transformer

500–25,000 KVA
through 69 KV

BIL (KV)
Unit Substation Transformer
112 1/2–2,500 KVA
through 38 KV


BIL (KV)
Pad Mounted Transformer 2,500 KVA and
smaller 34.5 KV and lower

BIL (KV)
1.2
2.5
5.0
8.7
15
25
34.5
46
69
45
60
75
95
110
150
200
250
350
45
45
75
95
110
150
200


45
60

95

150

TABLE 2

BIL REQUIREMENTS FOR LOW VOLTAGE RATINGS

Low Voltage Rating (Volts) BIL Substation Transformer (KV) BIL Padmount Transformer (KV) Insulation Class (KV)
208Y/120
240
460Y/277
480
45
45
45
45
30
30
30
30
1.2
1.2
1.2
1.2

TABLE 3

MINIMUM FAN COOLED RATINGS

Self Cooled (QA) KVA Self Cooled (QA) KVA Fan–Cooled (FA) Rating Fan–Cooled (FA) Rating
55 C 65 C (%) 55 C (%) 65 C (%)
501–2,499 112 115 128.8
2,500–10,000 112 125 140
Above 10,000 112 133.3 148.3

TABLE 4

CT ACCURACY CLASS REQUIREMENTS

Ratio Accuracy Class
600/5
1200/5
2000/5
3000/5
4000/5
C200
C400
C400
C400
C800

TABLE 5 DOCUMENTATION REQUIREMENTS FOR POWER TRANSFORMERS PER EP 13–4–1

Item Description Format As–Built
1 Complete certified structural drawings including but not limited to those items in Paragraph 7.2.1 See EP 2-5-2 Yes
2 Certified elementary diagrams for all equipment See EP 2-5-2 Yes
3 Certified detailed connection (wiring) diagrams per Paragraph 7.2.2 See EP 2-5-2 Yes
4 Certified listing of all nameplates provided including location identification per paragraph 7.2.4. See EP 2-5-2 Yes
5 Certified copies of all test reports to include requirements of Section 6.0 and those tests included in the purchase documents See EP 2-5-2 Yes
6 Complete certified installation, operating and maintenance manuals for all equipment/items provided, Paragraph 7.3.2 See EP 2-5-2 N/A