Inflection Point Engineering Section 13 — Electrical

Electric Bus Duct 480 Volt and Higher

IPE Engineering Practice IPE-EP-13-24-1

Document number: IPE-EP-13-24-1 · Section: 13 — Electrical

1.1

1.2

1.3

1.4

1.5

2.0

3.0

3.1

3.2

3.3

3.4

3.5

SCOPE

This Practice, including the Bus Duct 480 Volt and Higher Data Sheet, EP 13–24–1DS, covers requirements for assemblies of indoor and outdoor bus duct rated 480 Volt to 38 KV, 3 phase, 60 HZ for application on low resistance, high resistance, solidly grounded, or ungrounded systems, as specified on the Data Sheet. Bus duct shall conform to this Practice, unless written approval is obtained from IPE for exceptions.

This Practice is appropriate for attachment to an inquiry or purchase document when accompanied by the referenced IPE Engineering Practices and completed Data Sheets.

A revision bar indicates all changes made to this Revision.

Any deviation from this practice must be approved by the procedure described in EP 1–1–3.

An asterisk (*) indicates that a decision by the Owner’s Engineer or Owner is required, or that additional information is to be furnished by the Purchaser.

REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices EP 13–6–1 Medium Voltage Motor Controllers
EP 13–24–1DS Electric Bus Duct 480 Volt and Higher Data Sheet
ANSI Standards
C.37.23 Guide for Metal–Enclosed Bus and Calculating Losses in Isolated–Phase Bus
NFPA
National Electrical Code

DEFINITIONS

Contractor – Company or business that agrees to furnish materials or perform specified services at a specified price and/or rate to the Owner.

Inspector – A Inflection Point Engineering, LLC appointed engineer or inspector.

Manufacturer – The recipient of a direct or indirect purchase order for materials and/or equipment. In this context, a direct order is one issued to a Manufacturer by a Contractor or the Owner. An indirect order is one issued to a Manufacturer by a vendor (recipient of a direct order) for materials, fabricated components, or subassemblies.

Owner – Inflection Point Engineering, LLC.

Owner’s Engineer – A Inflection Point Engineering, LLC appointed engineer.

3.6 Purchaser – The party placing a direct purchase order. The Purchaser is the Owner’s designated representative.

4.0 SERVICE CONDITIONS

(*) Bus duct assemblies shall perform satisfactorily when installed and operated indoors or outdoors either intermittently or continuously in an atmosphere typical of petrochemical facilities. Unless otherwise noted, bus duct assemblies shall be suitable for use in a 104oF maximum ambient, -22oF minimum ambient, and at an altitude of 3,000 feet or lower.

DESIGN, CONSTRUCTION AND MATERIALS

1/8 inch or thicker material throughout.

In addition to the requirements of 5.2.1, outdoor sections of bus duct shall comply with and/or include the following:

In addition to 5.2.1 and 5.2.2, indoor sections of bus ducts may have ventilated enclosures. Ventilated enclosures shall meet the following additional requirements:

TESTING

Paragraph 6.2.1.1 rated frequency withstand test.

(*) When witness testing is specified, the Owner shall witness the complete testing of all items outlined in Section 6.0.

DRAWINGS AND DATA REQUIREMENTS

(*) All drawings provided for this equipment shall show equipment as specified and ordered. Typical drawings are not acceptable, unless they are revised to show only the equipment being furnished. Drawings shall be supplied in the quantities and the format shown on the Data Sheet.

SPARE PARTS

A complete priced spare parts recommendation based on the total purchase order is required within 60 days after the Manufacturer receives the purchase order. Spare parts recommendations shall include:

SHIPPING

10.0 TABLES

TABLE 1

NON-SEGREGATED PHASE BUS DUCT BIL

Nominal Voltage (KV) BIL (KV)
.480 45
2.4 - 4.16 60
13.8 95
34.5 200

TABLE 2 DOCUMENTATION REQUIREMENTS

FOR ELECTRICAL BUS DUCT 480 VOLT AND HIGHER PER EP 13–24–1

Item Description Format As–Built
1 Complete structural drawings per paragraph 7.2.1. See EP 2-5-2 Yes
2 Detailed connection (wiring) diagrams per paragraph 7.2.2. See EP 2-5-2 Yes
3 Support requirements and bus duct weight, moments, etc. per paragraph 7.1.4. See EP 2-5-2 Yes
4 Test reports for testing outlined in paragraph 6.3. See EP 2-5-2 Yes
5 Complete recommended, priced spare parts list, per paragraph 8.0. See EP 2-5-2 Yes
6 Installation, maintenance, and operating manuals per paragraph 7.3.2. See EP 2-5-2 Yes