Inflection Point Engineering Section 13 — Electrical

Induction Motor Repair

IPE Engineering Practice IPE-EP-13-23-1

Document number: IPE-EP-13-23-1 · Section: 13 — Electrical

Table 3 Shaft Vibration Limits Relative to Bearing Housing Using Noncontact Vibration Probes

.................................................................................................................................................................31

SCOPE

2.0 REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices
EP13–23–1DS Induction Motor Repair Data Sheet
ANSI/AFBMA Standards
Std. 9 Load Ratings and Fatigue Life for Ball Bearings
Std. 11 Load Ratings and Fatigue Life for Roller Bearings
ANSI/IEEE Standards
43 IEEE Recommended Practice for Testing Insulation Resistance of Rotating Machinery 95 IEEE Recommended Practice for Insulation Testing of Large AC Rotating Machinery with
High Direct Voltage
432 IEEE Guide for Insulation Maintenance for Rotating Electrical Machinery (5 HP to Less than 10000 HP)
API Standards
Std. 541 Form–Wound Squirrel Cage Induction Motors –– 250 HP and Larger
(Ref. Appendix C only).
NEMA Standards
MG–1 Motors and Generators

STANDARDS AND PUBLICATIONS (CONT.)

NFPA Standards
70 National Electrical Code
UL Standards
674 Electric Motors and Generators for Use in Hazardous Locations, Class I, Groups C
and D, Class II, Groups E, F and G.

DEFINITIONS

DAMAGE APPRAISAL

The following tests shall be performed as part of the incoming inspection and as part of the initial motor disassembly (Review this section prior to disassembly). The testing and order of disassembly shall be such as to aid in determining the motor quality and required repairs. A running test shall only be performed if in the judgment of the Contractor this is required and can be done without damage to the motor or the Contractor. Note: The tests below are not in any particular order of required performance. Specific information on testing is covered in Section

6.0 of this Practice. The incoming testing shall include but not be limited to:

5.4 for stator lead requirements.

MOTOR RECONDITIONING/REFURBISHING

Note: Sleeve bearings shall only be replaced when determined to be unserviceable/repairable and with specific approval by the Owner.

+0.002 (T).

Where: W= Journal Static weight Load ( Pounds )

N = Maximum Continuous Running Speed (RPM)

After all initial inspection and testing is complete and the rotor and bearings are declared serviceable, stator reconditioning may proceed as detailed below. Stator reconditioning shall only be applicable to stators that exhibit satisfactory serviceability without the need for a re– wind.

If the stator winding is determined to be unserviceable and the other critical motor parts serviceable, and in the Contractor’s judgment a motor rewind is justified, the motor may be rewound only if approved in writing by the Owner.

Note: Tapes utilizing one or more layers of polyethyelen terephthalate (PET) are unacceptable.

Note: Tapes utilizing one or more layers of polyethylene terephathalate (PET) are unacceptable.

5.4.5.1 above, and is to be scarfed or tapered to permit the joining of end turn insulation to the cell portion of the coil in a smooth manner. Cell wrappers are not permitted on any coil with a core length exceeding 25 inches, unless required by the motor Manufacturer.

Service Class F, 155°C
Wire insulation Single or double dacron–glass fiber fused over Class H film or armored (Kapton) film, if originally supplied.
Ground wall Mica flake, mica splittings, or mica paper with glass
Insulation Nomex, aramid or dacron backing
Slot liner Nylon paper, nomex, aramid
Wedges Preformed or molded fiberglass, glass fabric laminate with melamine or epoxy resin binder.
Filler strips Epoxy or polyester bonded glass laminate or molded fiberglass
Blocking Epoxy or polyester saturated dacron, nomex felt or glass mat.
Lacing Continuous filament glass roping cord, and glass tape. Shrink dacron/glass tapes are also acceptable. Tapes of dacron shall not be used.
Surge rings Resin filled fiberglass rope; soaked with a two part resin or B–stated (B–staged ropes must be fully cured by baking). Original rings can be used with new insulation.
Bus bar insulation Raychem heat shrinkable insulation.

TESTING

The following are descriptions of specific tests, test methods and acceptance criteria as referred to and/or referenced in this Practice.

Insulation resistance to ground testing shall be performed in accordance with the latest issue of IEEE 43. The test voltage shall be 1000 VDC (500 VDC for NEMA motors), with the test voltage applied for one minute prior to taking a reading. The minimum acceptable resistance to ground value is 2.0 Megohms for old windings and 10.0 Megohms for new windings. All readings shall be corrected to 40ºC. Motors that do not meet the above acceptance criteria may have windings that are wet. The windings may be dried out and the insulation resistance re–tested. The dry out temperature should not exceed 80 °C by thermometer and care must be taken to correct the winding resistance to 40°C since the core may be at a temperature much higher than ambient.

PI is the ratio of a ten minute to one minute insulation resistance reading to ground. As described above, the testing shall be done at 1000 VDC (500 VDC for NEMA motors) in accordance with latest issue of IEEE43. The minimum acceptable ratio is 2.0 for old windings and 3.0 for new windings. Temperature correction is not required for this test provided the stator core is at ambient temperature at time of test start and does not change appreciably during the test.

Surge comparison testing shall be performed to verify correctness of winding connections and to detect turn–to–turn insulation damage. Test voltage and test procedures shall be as recommended by the surge comparison test instrument Manufacturer. Surge comparison tests shall be done with the rotor removed.

Rotor balancing shall be accomplished as outlined in Section 5.2.4.

Maximum permissible shaft runout on standard length shaft extensions shall be as specified in NEMA MG–1, as follows:

Air gap measurements shall be taken at three locations (9, 12 and 3 o’clock) at both ends of the motor between the exterior of the rotor and interior of the stator. The percentage deviation (D) obtained from the formula below shall not exceed 10 percent at each end.

D  H  L 100

Where:

D = Percent deviation

H = Highest of the three readings at one end L = Lowest of the three readings at that end

A = The average of the three readings at that end

After the test run, both the inboard and outboard bearing oil shall be drained and inspected for discoloration. If discolored, sleeve bearings shall be inspected for damage. If bearings are replaced or reworked/fitted, a retest of the motor vibration and bearing temperature rise shall be accomplished.

Winding resistance shall be made with a low power, four lead resistance measurement device. Care should be taken not to apply high test current for long time periods that result in winding heat and incorrect comparative winding resistance values. Take readings between all leads, with a maximum 5% difference on OHMS allowed between any two pairs.

7.0 DATA/REPORT REQUIREMENTS

8.0 PREPARATION FOR SHIPMENT

9.0 TABLES

TABLE 1

MINIMUM RECOMMENDED GROUND WALL INSULATION THICKNESS

Volts Normal Thickness (inches) Minimum Thickness (inches)
2300 0.050 0.050
4160 0.065 0.060
6900 0.100 0.090

TABLE 2

BEARING HOUSING VIBRATION LIMITS FOR COMMON OPERATING SPEEDS

Synchronous Speed (RPM) Maximum Unfiltered Velocity
Zero–to–Peak (inches per second) (1),(2)
720
900
1200
1800
3600
0.060
0.075
0.10
0.10
0.10

NOTES:

TABLE 3

SHAFT VIBRATION LIMITS RELATIVE TO BEARING HOUSING USING NONCONTACT VIBRATION PROBES (1)

Synchronous Speed (RPM) Unfiltered Radial Shaft Displacement Peak–to–Peak (mils) (1)
v1200 1800
3600
1.5
1.5
1.5

NOTES: