Inflection Point Engineering Section 13 — Electrical

Electrical Equipment Inspection and Testing

IPE Engineering Practice IPE-EP-13-2-2

Document number: IPE-EP-13-2-2 · Section: 13 — Electrical

1.0

1.1

1.2

1.3

1.4

1.5

1.6

2.0

SCOPE

This Practice along with the other IPE Engineering Practices provides details for field inspection and testing of electrical equipment at Owner plants and associated facilities. Forms to report testing results are contained in EP 13-2-3 .

This Practice covers the requirements necessary to insure that plant electrical equipment complies with applicable codes, standards and contract documents.

This Practice will be applicable to both new facilities, modernization and repair of existing facilities.

All IPE Engineering Practices are to be used in conjunction with this Practice to provide the complete field inspection and testing requirements.

Any deviation from this Practice must be approved by the procedure described in EP 1-1-3. A revision bar indicates all changes made to this Revision.

REFERENCES

The latest published edition of the following Standards and Codes shall be used with this Practice:

STANDARDS AND PUBLICATIONS

STANDARDS AND PUBLICATIONS (Continued)

IPE Engineering Practices (Cont.)
EP 13-13-1 Electrical Standards for Packaged Equipment EP 13-14-1 Motor Connection Drawings
EP 13-15-1 Equipment Grounding Details EP 13-16-1 Electrical Equipment Shelters EP 13-17-1 Uninterruptible Power Supply EP 13-19-1 Low Volt Auto Transfer Switches
EP 13-21-1 High Voltage Oil, Vacuum, and SF6 Outdoor Circuit Breakers 13.8 KV and Above
EP 13-22-1 Actuators for Motor Operated Valves
EP 13-25-1 Medium Voltage Metal Enclosed Switches (ME Switches)
EP 13-13-1 Electrical Standards for Packaged Equipment EP 13-14-1 Motor Connection Drawings
EP 13-15-1 Equipment Grounding Details EP 13-16-1 Electrical Equipment Shelters EP 13-17-1 Uninterruptible Power Supply EP 13-19-1 Low Volt Auto Transfer Switches
EP 13-21-1 High Voltage Oil, Vacuum, and SF6 Outdoor Circuit Breakers 13.8 KV and Above
EP 13-22-1 Actuators for Motor Operated Valves
EP 13-25-1 Medium Voltage Metal Enclosed Switches (ME Switches)
ANSI Standards ANSI Standards
C2 National Electrical Safety Code
C37 Circuit Breakers, Switchgear, Relays, Substations and Fuses C57 Distribution, Power and Regulating Transformers
C84.1 Voltage Ratings for Electric Power Systems and Equipment
C2 National Electrical Safety Code
C37 Circuit Breakers, Switchgear, Relays, Substations and Fuses C57 Distribution, Power and Regulating Transformers
C84.1 Voltage Ratings for Electric Power Systems and Equipment
ANSI/EEE Standards ANSI/EEE Standards
Std 80 Guide for Safety in AC Substation Grounding
Std 141 Recommended Practices for Electrical Power Distribution for Industrial Plants
Std 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems Std 242 Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems
Std 399 Recommended Practice for Industrial and Commercial Power System Analysis
Std 400 Guide for Making High-Direct-Voltage Tests on Power Cable Systems in the Field Std 446 Recommended Practice for Emergency and Standby Powers for Industrial and
Commercial Applications
Std 576 Recommended Practice for Installation, Termination and Testing of Insulated Power Cables Used in the Petroleum and Chemical Industry
Std 80 Guide for Safety in AC Substation Grounding
Std 141 Recommended Practices for Electrical Power Distribution for Industrial Plants
Std 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems Std 242 Recommended Practice for Protection and Coordination of Industrial and
Commercial Power Systems
Std 399 Recommended Practice for Industrial and Commercial Power System Analysis
Std 400 Guide for Making High-Direct-Voltage Tests on Power Cable Systems in the Field Std 446 Recommended Practice for Emergency and Standby Powers for Industrial and
Commercial Applications
Std 576 Recommended Practice for Installation, Termination and Testing of Insulated Power Cables Used in the Petroleum and Chemical Industry
API API
RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class 1, Division 1, and Division 2.
RP 540 Electrical Installation in Petroleum Processing Plants
RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class 1, Division 1, and Division 2.
RP 540 Electrical Installation in Petroleum Processing Plants

STANDARDS AND PUBLICATIONS (Continued)

NEMA
MG-1 Motors and Generators
NFPA
NFPA-70 National Electrical Code
Plant Standard Operating Procedures
SOP# 10-0201001 Predictive and Preventative Maintenance Manual for Electrical Equipment
Regulations
Applicable State and Local Codes
Occupational Safety and Health Administration (OSHA)
National Board of Fire Underwriters for Electrical Wiring and Apparatus

3.0

3.1

3.2

3.3

3.4

3.5

3.6

3.7

3.8

3.9

3.10

3.11

3.12

DEFINITIONS

Calibrate/Set - Refers to the application of a set point to a device and verify the setting/response by application of a known test quantity.

Check - Visual inspection, used to insure conformance with drawings and specifications.

Contractor - Company or business that agrees to furnish materials or perform specified services at a specified price and/or rate to the Owner.

Function (Functional) Check - Refers to the verification of the proper operation of a system (e.g. complete control scheme).

Inspect/Inspection - A detailed visual inspection that will require removal of covers, etc. to insure conformance to drawings and specifications.

Inspector - A Inflection Point Engineering, LLC appointed engineer or inspector.

Manufacturer - The recipient of a direct or indirect purchase order for materials and/or equipment. In this context, a direct order is one issued to a Manufacturer by a Contractor or the Owner. An indirect order is one issued to a Manufacturer by a vendor (recipient of a direct order) for materials, fabricated components, or subassemblies.

Owner - Inflection Point Engineering, LLC.

Owner's Engineer - A Inflection Point Engineering, LLC appointed engineer.

Purchaser - The party placing a direct purchase order. The Purchaser is the Owner's designated representative.

Verify - To prove by operation, measurement, or other means that equipment operates and/or is adjusted properly.

Test - A method or process used to verify the quality of equipment usually by/with the application of voltage/current.

4.0

4.1

4.2

4.2.1

4.2.2

4.2.3

4.3

4.3.1

4.3.2

4.3.3

4.3.4

4.3.5

4.4

4.4.1

4.4.2

4.5

4.5.1

4.5.2

GENERAL DESCRIPTION AND REQUIREMENTS

Qualification of Inspection and Testing Personnel

All electrical equipment inspectors and testing personnel must be approved by the Owner.

Test Equipment Requirements

All test equipment must be calibrated and suitable for the task. Must be on a six month recalibration cycle.

Must have a current calibration tag affixed to the test equipment.

Calibration must be traceable back to the National Bureau of Standards.

Drawings and Equipment Instruction Books

Only the most current "for construction" drawings and equipment Manufacturers "as-builts" drawing shall be used for inspection and testing.

Electrical equipment instruction books shall be used in conjunction with project specified

IPE Engineering Practices and contract documents.

Field verification of scale dimensions on plan drawings is required since locations, distances and levels will be governed by actual field conditions. The electrical plan drawings are diagrammatic in nature and do not indicate exact and complete routes of raceways and wirings.

All drawings, shall be reviewed before starting work including structural, concrete, piping, instrumentation and vendor's drawings to ascertain any conflicts of interferences with electrical equipment. If any instances arise where such interferences are found, they shall be immediately reported to the Owner or Owner's Engineer.

One complete set of drawings shall be maintained exclusively for record purposes and all significant code changes, modifications, and additions shall be noted and shown; this set of drawings shall be given to the Owner upon completion of the electrical work.

Area Classification

The installation shall be in strict compliance with the construction drawings, the National Electrical Code and API 500. When conflicts and/or drawing omissions occur the Owner shall be responsible for resolution and/or changes.

Field inspection shall verify that the complete installation and all equipment meet the area classification requirements.

Handling and Storage

All electrical equipment shall be lifted, moved, stored in strict compliance with the Manufacturer's (and contract document) requirements.

All lifting, handling and moving of fabricated/engineered electrical equipment (i.e. power transformers, switchgear, large frame motors) shall be witnessed by the Owners field inspector or Owner approved designate.

4.7 Forms and Check Lists (Inspection and Testing)

Forms and checklist for the inspection and testing of electrical equipment are listed in EP 13-2-3. Contractors test forms may be used after review and approval by the Owner.

FIELD INSPECTION AND TESTING OF ELECTRICAL EQUIPMENT

This section details the minimum required field inspection and testing of electrical equipment operation and installation. The requirements are general in nature and shall be supplemented with specified additional requirements as outlined in the Manufacturer's instruction manuals.

Electric Motors Electric Motors
Motor Voltage 460 volts
2400 volts and greater
Test Voltage 1000 volts
2500 volts
Electrical Power and Control Cable Electrical Power and Control Cable
Cable insulation voltage rating 600 volts
above 600 volts
Test voltage 1000 volts
2500 volts
Power Transformers Power Transformers
Winding voltage (nominal) 480 volts
above 480 volts
Test Voltage 1000 volts
2500 volts
Electrical Equipment (general) Electrical Equipment (general)
Equipment voltage level (nominal) 120/208 VAC
480 VAC
500 VAC to 5000 VAC
Above 5000 VAC
Test Voltage 500 volts
1000 volts
2500 volts
5000 volts

In addition to the Manufacturer's field testing requirements the following tests shall be performed.

Close and trip circuit breaker from its local and remote devices and each protective device.

In addition to applicable items in 5.2.1, 5.2.2, and 5.2.3 above, perform the following:

5.15 of this Practice.

P.I. ratio of 3. The minimum insulation resistance value shall be per the bus duct Manufacturer's recommendations.

Low voltage circuit breaker integral solid-state or electromechanical protective devices shall be tested in accordance with the Manufacturer's instructions using primary (full) current and shall include the following:

Test insulation resistance (megger) of each lighting power conductor phase to phase and phase to ground prior to termination at the fixture.

Inspection and testing requirements shall be in accordance with EP 13-12-1.

Function check each equipment item under simulated operations by actuating each device, either by artificial loading, connecting temporary jumpers, opening of wire circuit or manual operation of switch - verify proper operation of all auxiliary items.

Equipment installation inspection items: