Inflection Point Engineering Section 13 — Electrical

Electrical Detail Design and Construction Practice

IPE Engineering Practice IPE-EP-13-2-1

Document number: IPE-EP-13-2-1 · Section: 13 — Electrical

RECEPTACLES 31

13.0 CATHODIC PROTECTION 32

14.0 FIRE ALARM 32

ELECTRIC HEAT TRACING 32

DRAWINGS 33

TABLES 36TABLES 36

Table 1 Minimum Sizes of Ground Conductors 36Table 1 Minimum Sizes of Ground Conductors 36

Table 2 Instruments Per Branch Circuit 36Table 2 Instruments Per Branch Circuit 36

Table 3 Device Mounting Height 36Table 3 Device Mounting Height 36

Table 4 Required Location For Expansion Fittings 37Table 4 Required Location For Expansion Fittings 37

Table 5 Minimum Cable Installation Temperature 37Table 5 Minimum Cable Installation Temperature 37

Table 6 Power Cables Without Metallic-Shielding or Armor 38Table 6 Power Cables Without Metallic-Shielding or Armor 38

Table 7 Welding Receptacle Cable Ampacity 39Table 7 Welding Receptacle Cable Ampacity 39

Table 8 Tray Spacing (Inches) 39Table 8 Tray Spacing (Inches) 39

Table 9 Tray-Conduit Spacing (Inches) 40Table 9 Tray-Conduit Spacing (Inches) 40

Table 10 Conduit Spacing (Inches) 41Table 10 Conduit Spacing (Inches) 41

Table 11 Ladder Type Cable Tray Load/Span Class Designations 42Table 11 Ladder Type Cable Tray Load/Span Class Designations 42

1.0

1.1

1.2

1.3

1.4

1.5

2.0

2.1

SCOPE

This Practice, along with IPE Engineering Practices, provides the detail design and installation requirements of Electrical Power Systems for facilities at process plants, laboratories, pump stations, buildings, etc. It is basically written for use by the engineering contractors design group, but can also supplement field design and installation engineers in understanding the Owner preferences and practices.

This Practice will be applicable to both new facilities and the modernization of existing facilities.

EP 13-1-1 for Power System Design, is to be used in conjunction with this Practice to provide the complete design from conception to detail design and construction requirements.

Any deviation from this Practice must be approved by the procedure described in EP 1-1-3. A revision bar indicates all changes made to this Revision.

REFERENCES

The latest published edition of the following standards and codes are referenced herein.:

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1-1-3 Deviations to IPE Engineering Practices EP 12-1-1 Control Systems
EP 13-1-1 Power System Design Practices
EP 13-2-2 Electrical Equipment - Field Inspection and Testing EP 13-8-1 Wire and Cable 600 Volt and Below
EP 13-8-2 Power Cable 5KV and Above
EP 13-15-1 Equipment Grounding Details
ASTM
C33 Standard Specification for Concrete Aggregate
ANSI Standards
C2 National Electrical Safety Code
C80.1 Rigid Steel Conduit, Zinc Coated C80.5 Rigid Aluminum Conduit
ANSI/IEEE Standards
Std 576 IEEE Recommended Practice for Installation, Termination and Testing of Insulated
Power Cable as used in the Petroleum and Chemical Industry.

STANDARDS AND PUBLICATIONS (Cont.)

API Standards
RP 500 Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class 1, Division 1 and Division 2
RP 540 Electrical Installations In Petroleum Processing Plants
IEEE Standards
Std 80 Guide for Safety in AC Substation Grounding
Std 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems Std 518 IEEE Guide for the Installation of Electrical Equipment to Minimize Electrical
Inputs to Controllers From External sources
NFPA Codes
70 National Electrical Code
496 Purged and Pressurized Enclosures for Electrical Equipment
497 Recommended Practice for The Classification of Flammable Liquids, Gases, or Vapors and Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas.
Trade Standards
Inflection Point Engineering, LLC is in general agreement with the latest published editions of standards of API, and etc.
UL
1 Flexible Metal Conduit
6 Rigid Metallic Conduit
651 Schedule 40 and 80 Rigid PVC Conduit

DEFINITIONS

POWER SYSTEM

GROUNDING SYSTEM

INSTRUMENT SYSTEM

Refer to EP 12-1-1 "Control Systems".

S - Special handling of special levels may require spacing of conduits and trays, such as signals from communicating fields, or signals from power greater than 1000V or greater than 800A or both. NOTE: Other class codes are described in IEEE Std. 518.

LIGHTING AND 120 VOLT POWER SYSTEMS

AREA CLASSIFICATION

POWER AND (NON-INSTRUMENTATION) CONTROL WIRING

CONDUIT AND TRAY SYSTEMS

NEMA VE-1, paragraph 2.3.2.3. Larger depths may be used, if required, to accommodate the size and quantities of cables in the tray.

WIRE AND CABLE

For additional requirements see EP 13-1-1 and EP 13-8-1.

Tm = Maximum pulling tension in lbs. N = Number of conductors in cable

CM = Circular mil area of each conductor

RECEPTACLES

480 volt welding receptacles with circuit breakers shall be suitable for the classification of the area where installed and compatible with the existing receptacles at the location to be installed.

13.0 CATHODIC PROTECTION

Cathodic protection is not required, unless specified otherwise in the project scope document.

14.0 FIRE ALARM

A fire alarm system is generally not required, unless specified otherwise in the project scope document.

ELECTRIC HEAT TRACING

DRAWINGS

The following construction drawings and documents are required:

TABLES

TABLE 1

MINIMUM SIZES OF GROUND CONDUCTORS

Main Ground Loop Equipment Grounds
Substation Ground Loop/Grid
2/0 AWG (70 MM2)

6 AWG (16 MM2)

4/0 AWG (120 MM2) (1)

NOTE:

TABLE 2 INSTRUMENTS PER BRANCH CIRCUIT

Type Number
Controllers or Recorder Controller Electric Recorders
Chart Drives
Multipoint Temperature Indicator Data Logger
Temperature Scanner Analyzers
Alarm Panels
1
6
10
1
1
1
1
1

TABLE 3

DEVICE MOUNTING HEIGHT

Lighting Fixtures
Switches X.P. & Gen. Purpose
X.P. Receptacle
Receptacles in Offices
Thermostats

Telephone Outlets
As shown on the Plans
4 ft. 6 in. above floor
4 ft. 0 in. above floor

1 ft. 6 in. above floor

5 ft. 0 in. above floor

1 ft. 6 in. above floor

TABLE 4

REQUIRED LOCATION FOR EXPANSION FITTINGS

Galvanized Steel
Aluminum
Non metal
200 feet

100 feet

50 feet

TABLE 5

MINIMUM CABLE INSTALLATION TEMPERATURE

Type of Insulation or Jacket Minimum Temperature
PVC
EPR
Polyethylene
20°F

0°F

20°F

TABLE 6

POWER CABLES WITHOUT METALLIC-SHIELDING OR ARMOR

Thickness of Insulation
(64th's of inch)
O.D. of Cable, (Inches) O.D. of Cable, (Inches) O.D. of Cable, (Inches)
1.000 & Less 1.000 to 2.00 2.001 & Over
10 and Less 4 5 6
11 to 20 5 6 7
21 and Over 7 8

POWER CABLES WITH METALLIC SHIELDING OR ARMOR

Flat Type & Wire Armor 12
Tape/Wire Shielded Cables 12
Type MC Cables without Shield 7

CONTROL CABLES AND FLEXIBLE PORTABLE CABLE

Control Cables and Flexible Portable Cables 8

TABLE 7

WELDING RECEPTACLE CABLE AMPACITY

Number of Outlets per Circuit Minimum Current Capacity of Branch Circuit
4 or less 100 amperes

TABLE 8

TRAY SPACING (INCHES)

Level 1 2 3 3S 4 4S
1 0 See Note 3 6 6 26 26
2 See Note 3 0 6 6 18 26
3 6 6 0 0 See Note 4 12
3S 6 6 0 0 8 18
4 26 18 See Note 7 8 0 0
4S 26 26 12 18 0 0

NOTES:

TABLE 9

TRAY-CONDUIT SPACING (INCHES)

Level 1 2 3 3S 4 4S
1 0 1 4 4 18 18
2 1 0 4 4 12 18
3 4 4 0 0 0 8
3S 4 4 0 0 6 12
4 18 12 0 6 0 0
4S 18 18 8 12 0 0

NOTES:

TABLE 10 CONDUIT SPACING (INCHES)

Level 1 2 3 3S 4 4S
1 0 1 3 3 12 12
2 1 0 3 3 9 12
3 3 3 0 0 0 6
3S 3 3 0 0 6 9
4 12 9 0 6 0 0
4S 12 12 6 9 0 0

NOTE:

This Table indicates the minimum distance in inches between outside surfaces of conduits being run induct banks. This also applies to the distance between trays or conduits and power equipment of less than 100 KVA.

TABLE 11 LADDER TYPE CABLE TRAY LOAD/SPAN CLASS DESIGNATIONS

Working Load Working Load Support Span Feet (m) Support Span Feet (m) Class Designation Per NEMA VE-1
lbs./ft. [kg/m] Feet [m]
75 [111.6] 8 [2.44] 8B
100 [148.8] 8 [2.44] 8C
75 [111.6] 12 [3.66] 12B
100 [148.8] 12 [3.66] 12C
75 [111.6] 16 [4.87] 16B
100 [148.8] 16 [4.87] 16C
75 [111.6] 20 [6.09] 20B
100 [148.8] 20 [6.09] 20C

NOTES: