Inflection Point Engineering Section 11 — Refractory, Insulation & Fireproofing

Insulation Application - Tanks and Spheres

IPE Engineering Practice IPE-EP-11-3-4

Document number: IPE-EP-11-3-4 · Section: 11 — Refractory, Insulation & Fireproofing

FIGURE 7 "BELT LOOP" DETAIL 28

FIGURE 8 TANK PENETRATION INSULATION DETAILS 29

FIGURE 9 TERMINATION OF POLYURETHANE FOAM 30

FIGURE 10 EXPANSION JOINT AND BONDING DETAILS 31

FIGURE 11 STIFFENER RING INSULATION 32

FIGURE 12 SHEATHING AT STIFFENERS 33

FIGURE 13 FLASHING AT NOZZLES AND OTHER PROJECTIONS 34

FIGURE 14 FOAM SURFACES COMPARED 35

1.0

1.1

1.2

1.3

1.4

1.5

2.0

SCOPE

This Practice covers the mandatory requirements for the materials and application of external insulation to outdoor storage tanks and spheres designed in compliance to EP 9-1-1, EP 9-2- 1 and EP 9-4-1.

Any deviation from this Practice must be approved by the procedure described in EP 1-1-3.

This Practice is appropriate for attachment to an inquiry or purchase document when accompanied by the referenced IPE Engineering Practices and the completed data sheets included in EP 11-3-4 DS, as required.

An asterisk (*) indicates that a decision by the Owner is required, or that additional information shall be furnished by the purchaser.

A revision bar indicates all changes made to this Revision.

REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1-1-3 Deviations to IPE Engineering Practices EP 9-1-1 Atmospheric Storage Tanks
EP 9-1-2 Welding Requirements for Atmospheric Storage Tanks EP 9-2-1 Low Pressure Storage Tanks
EP 9-4-1 Pressure Storage Spheres EP 10-3-1 Shop Painting
EP 11-3-4 DS Insulation Application - Tanks and Spheres Data Sheet EP 11-3-6 Insulation of Flanged Joints and Valves in Hot Service
API
Std 650 Welded Steel Tanks for Oil Storage
ASTM
A167 Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet and Strip
B209 Specification for Aluminum and Aluminum-Alloy Sheet and Plate
C449 Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement C533 Calcium Silicate Block and Pipe Thermal Insulation
C55 Cellular Glass Block and Pipe Thermal Insulation
C591 Unfaced Preformed Rigid Cellular Polyurethane Thermal Insulation C592 Mineral Fiber Blanket Insulation
C612 Mineral Fiber Block and Board Insulation

STANDARDS AND PUBLICATIONS (CONTINUED)

ASTM (Continued)
C795 Wicking Type Thermal Insulation for Use Over Austenitic Stainless Steels C892 High Temperature Fiber Blanket Thermal Insulation
C929 Handling, Transporting, Shipping, Storage, Receiving, and Application of Thermal Insulation Materials to be Used Over Austenitic Stainless Steel
D756 Determination of Weight and Shape Changes of Plastics Under Accelerated Service Conditions
D1621 Test Method for Compressive Properties of Rigid Cellular Plastics D1622 Apparent Density of Rigid Cellular Plastics
D2126 Response of Rigid Cellular Plastics to Thermal and Humid Aging D2856 Open Cell Content of Rigid Cellular Plastics by the Air Pycnometer.
E84 Surface Burning Characteristics of Building Materials
SSPC
SP 6 Commercial Blastcleaning

DEFINITIONS

DRAWING AND INSULATION SCHEDULES

(*)Drawing and insulation schedules shall be supplied to the contractor by the Owner's Engineer and shall contain the following information:

DOCUMENTATION

The following data, as applicable, shall be submitted to purchaser for approval by the Owner's Engineer.

The Owner's Engineer shall supply a supplemental job specification to the insulation contractor. The job specification shall include all applicable drawing and insulation schedules, material specifications, and all obligations and responsibilities required for the job.

ACCEPTABLE MATERIALS

6.2

6.2.1

6.2.2

6.2.3

6.2.4

6.2.5

6.2.6

6.2.7

6.2.8

Insulated tanks which require fireproofing shall have calcium silicate as the outside layer of insulation. Alternate designs using a combination of passive fireproofing materials and insulation must be approved by the Owner's Engineer and a PSM representative.

Insulation for noise control shall be limited to fiberglass (6-8 lb./ft.3) or mineral wool (8-10 Ib./ ft.3). The requirements in Section 7.10 shall also apply.

Rigid and Resilient Insulation

Calcium silicate block insulation shall be suitable for 1200F and comply with ASTM C533, Type 1 requirements. For fire exposed areas, calcium silicate shall be manufactured to withstand at least 1800F and shall comply with ASTM C533, Type 2.

Mineral wool shall have a neutral pH, a nominal density not less than 8 lb/cu. ft. and be suitable for 1200F, except as noted. Additional requirements are:

Cellular glass shall conform to ASTM C552 and is limited to a maximum service temperature of 450F.

Alumina silica ceramic fiber blanket shall conform to ASTM C892 with a density of 8 lb/cu. ft. and a maximum use temperature of 2300F.

Insulating cement shall be mineral fiber ASTM C449. Cement shall set to a hard smooth monolithic finish.

Polyurethane foam shall comply with ASTM C591, Type II, with a flame spread rating not exceeding 25 per ASTM E84. For roof applications, and areas of high traffic, foam must have a minimum compressive strength (parallel to rise) of 40 psi. Polyurethane foam is limited to a maximum service temperature of 175F.

Fiberglass shall be limited to a maximum service temperature of 850F. Block and board insulation shall have a minimum density of 6 lb/ft3 and comply with ASTM C612, type III.

Perlite shall comply with ASTM C610, Type II material, and shall have a sodium silicate binder. The material shall also be subjected to a high temperature test (1200F), and be checked for smoking, charring, cracking, and other signs of physical deterioration.

6.3

6.3.1

6.3.2

6.3.3

6.3.4

6.3.5

6.3.6

6.3.7

6.3.8

equal.

6.4

6.4.1

Insulation Coverings

Weatherproofing jacket for non-fire exposed areas, except for those items which comply with Section 6.3.2 , shall be aluminum according to the following:

Weatherproof covering for fire exposed areas, equipment of low melting alloys, or polyurethane foam within a process unit, shall be 0.01 inch thick stainless steel ASTM A167, Type 316.

Covering steel shall be according to the following:

Fireproofing mastic shall be a breather type, asbestos free, with a flame spread of 4 or less (Vimasco WC-1 or equal).

All jacketing materials shall have a vapor barrier of colored converted epoxy, colored polyethylene, or 50-pound polyethylene-kraft paper moisture barrier 100 percent bonded to the inside surface. When specified on the insulation schedules, the outside of the jacketing shall be coated with a color converted epoxy.

Insulation systems on low melting alloys (such as aluminum), or on equipment where the system is considered as fireproofing, shall be capable of withstanding the force of firehose stream impingement.

Elastomeric coatings shall be used over cellular glass insulation when metal jackets are not provided.

Applied coatings of mastic or elastomeric materials shall comply with the following:

Mastic Weathercoat shall be a vinyl acrylic Childers Vicryl IPE -10/IPE- 11-1 or

Accessories

Bands shall be stainless steel, Type 316, annealed temper. Sizes shall be 3/4 inch wide by

0.020-inch minimum thickness, with wing type seals. Breather springs shall be used where required for expansion. Bands shall be held in place with screwed keepers.

nonasbestos containing insulation. Bands on asbestos containing insulation shall be color coded yellow.

SPECIAL REQUIREMENTS

INSULATION SUPPORTS

APPLICATION

9.4

9.4.1

9.4.2

9.4.3

9.4.4

9.4.5

9.4.6

9.5

9.5.1

9.5.2

9.5.3

9.5.4

9.5.5

9.5.6

9.5.7

9.5.8

For polyurethane foam applications wrap steam lines, or other items operating above the foam temperature limit with 1 inch thick fiberglass blanket prior to the foam application.

Access and Clearance

A minimum clearance of 4 inches between the outside of any insulation and adjacent equipment, piping, or structural members shall be maintained. This clearance shall take into account the thickness of any fireproofing coating or insulation applied to such adjacent equipment, piping, or structural members.

Insulation systems shall permit access to parts requiring maintenance without requiring destruction of the entire insulation system.

Insulation at flanged joints shall be tapered to permit stud removal without damage to the insulation. Nozzles shall be extended, by the insulation thickness (min.), to ensure clearance for bolting.

Edges of insulation openings such as around manholes, nozzles, cutouts for stud removal, pipe supports, and other attachment, shall be sealed to prevent water from entering. Metal covers shall be used if temperatures are beyond the usable range of weatherproofing coatings.

Nameplates (including code inspection plates) shall not be insulated. Insulation surrounding these plates shall be beveled away from such markings and sealed to prevent water from entering.

Manway covers shall be provided when units are insulated with polyurethane foam. The covers shall be removable and comply with EP 11-3-6.

Application of Board, Block or Blanket Insulation

All insulation shall be installed butted together and shall be either impaled on studs or banded to the shell.

Each layer of insulation shall be installed with transverse or longitudinal joints staggered.

If more than one layer of insulation is applied, each layer shall be secured in place, and joints of each layer offset.

All gaps shall be filled with insulating cement. Except, when insulating stainless steel use blanket insulation to point-up the cracks.

Spacing of clips or pins for securing insulation on vertical surfaces shall be on no more than 16 inch centers for blanket insulation. Block insulation shall be installed with no less than 2 studs (clips or pins) per block. The insulation shall be secured by lacing wire to the pins.

When dual layer insulation systems employing different insulation materials are used for combined thermal and noise control, the insulation for noise control shall be installed as the outer layer.

Install each panel of board or blanket insulation in a slightly compressed condition in both directions.

Insulation shall be installed in two staggered layers of nearly equal thickness if:

Extreme caution shall be taken to prevent spraying in the presence of water, rain, fog, condensation, etc., or wind velocities above 12 miles per hour. All applications shall stop under these conditions. (Shielded scaffolds or wind breaks can be used to allow spraying during high wind velocity with approval of Owner's Engineer). Foam shall not be applied when the ambient temperature is below 60F. The weather forecast shall be checked each day prior to commencing application.

The foam shall be applied in minimum 1/2 inch, maximum one (1) inch thick passes to reach the desired insulation thickness with a tolerance of -0 inch, +1/4 inch nominal foam thickness. The contractor shall gauge the foam for proper thickness at least once every 100 square feet applied. In areas where obstacles do not allow proper spray techniques, this tolerance cannot be adhered to and the minimum thickness shall apply. The completed job shall be monolithic.

The finished surface of the foam shall be smooth textured (orange peel appearance) and free from overspray, blow holes, and soft, spongy, or friable areas. Surfaces that are rougher than the acceptance criteria and are over 2 ft2 in area shall be planed smooth and resprayed to provide a smooth surface. Foam degraded by ultraviolet (UV) light must be removed. Any surface "dusting" due to UV attack shall be brushed off prior to coating application.

Any depressions in horizontal or nearly horizontal surfaces that will trap more than 1/4 inch of water over an area larger than 11 ft2 shall be filled with foam prior to the coating application.

Roof projections: All items projecting through the roof structure such as vents, pipes, or conduits shall have the urethane foam carried in a smooth transition to a minimum of 6 inches up the side of any projection of parapet. Extreme caution must be used to prevent blocking or interfering with functionality of breather vents.

Projections on vertical and spherical shells shall have the foam carried in a smooth transition to a minimum of 3 inches up/onto the projection. See Figure 8.

Insulation shall be tapered around flanges, manholes, valves, gage glasses, instruments, etc., to allow for maintenance and equipment operation.

For above ambient temperature service tanks, the foam shall be tapered to terminate above the bottom of the shell. See Figure 9. If the roof is uninsulated, the foam shall be tapered to terminate below the top of the shell.

WEATHERPROOFING

APPLICATION FOR FIRE PROTECTION

Application of combined thermal insulation and fireproofing shall be per Sections 9.0 and 10.0 with the following additions:

INSPECTION

Prior to spraying foam on the substrate, each spray mechanic shall spray a 4 foot x 4 foot test panel to meet the criteria of paragraph 9.6.12. The samples shall be inspected for visual compliance with Figure 14. One panel shall be selected to serve as the standard of performance for the work.

13.0 POLYURETHANE FOAM GUARANTEE

The installation shall be guaranteed for a period of five years from the date of acceptance against blistering, cracking, peeling, or stripping caused by inherent defects of the installed materials.

14.0 TABLES

TABLE 1 DOCUMENTATION REQUIREMENTS FOR INSULATION APPLICATION PER EP 11-3-4

Item Description Format As-Built
The following information shall be shown on drawings and included in job specifications: The following information shall be shown on drawings and included in job specifications: The following information shall be shown on drawings and included in job specifications: The following information shall be shown on drawings and included in job specifications:
1 Product specifications See EP 2-5-2 Yes
2 Material storage requirements, including shelf life and temperature. See EP 2-5-2 Yes
3 Design and application details of insulation expansion joints. See EP 2-5-2 Yes
4 Repair procedures for damaged areas. See EP 2-5-2 Yes
5 Inspections and testing procedures. See EP 2-5-2 Yes
6 Recommended safety precautions, such as proposed method of electrical grounding of equipment (i.e, blast cleaning and spray application). See EP 2-5-2 Yes
7 Contractor Specification
The Owner's Engineer shall supply a supplemental job specification to the insulation contractor. The job specification shall include all applicable drawing and insulation schedules, material specifications and all obligations and responsibilities required for the job.
See EP 2-5-2 Yes
8 Qualifications of Foam Applicators
Foam shall be installed only by foam applicators who are experienced in the proposed application methods and who use equipment with positive metering.
See EP 2-5-2 Yes
9 The foam spray mechanics shall have a minimum of two years' field spraying experience. See EP 2-5-2 Yes

TABLE 1 (CONT'D) DOCUMENTATION REQUIREMENTS

FOR INSULATION APPLICATION PER EP 11-3-4

Item Description Format As-Built
10 Bidders shall submit a listing of similar installations completed by them, including type of foam and weather protection, date of completion, location, and contacts.
If the proposed foam or protective coating has not been used by a bidder, he shall submit a listing of successful installations by others and a confirmation that the manufacturer(s) will furnish field assistance.
See EP 2-5-2 Yes
11 Bidders shall submit resumes of recent experience of those supervisory personnel and spray mechanics that will be used on the job. See EP 2-5-2) Yes

15.0 FIGURES

FIGURE 1 "S" CLIP

Figure

NOTE: Length (L) to equal overlap of jacketing per Section 10.

FIGURE 2 INSULATION STUDS AND CLIPS

Figure

NOTES:

FIGURE 3 INSULATED FIXED ROOF TANKS

Figure

NOTES:

FIGURE 4

SHELL-TO-ROOF ANGLE

Figure

FIGURE 5

DETAILS FOR INSULATED FIXED ROOF TANKS

Figure

NOTE: For notes see Figure 3.

FIGURE 6

SPACING OF CLIPS ON SPHERES

Figure

NOTE:

Dimensions shown are maximum and shall be measured on periphery.

FIGURE 7

"BELT LOOP" DETAIL

Figure

FIGURE 8

TANK PENETRATION INSULATION DETAILS

Figure

FIGURE 9

Figure

TERMINATION OF POLYURETHANE FOAM

Figure

FIGURE 10

EXPANSION JOINT AND BONDING DETAILS

Figure

FIGURE 11

STIFFENER RING INSULATION

Figure

FIGURE 12

SHEATHING AT STIFFENERS

Figure

FIGURE 13

FLASHING AT NOZZLES AND OTHER PROJECTIONS

Figure

NOTE:

Care should be taken to insure that there is no path for moisture between the corrugations on the underside of the nozzle.

FIGURE 14

FOAM SURFACES COMPARED

Figure