Inflection Point Engineering Section 11 — Refractory, Insulation & Fireproofing

Fired Heater Refractory

IPE Engineering Practice IPE-EP-11-1-2

Document number: IPE-EP-11-1-2 · Section: 11 — Refractory, Insulation & Fireproofing

Table 6 Documentation Requirements For Fired Heater Refractory 25Table 6 Documentation Requirements For Fired Heater Refractory 25

22.0 FIGURES 26

Figure 1 Nose Detail 26Figure 1 Nose Detail 26

Figure 2 Access Door 26Figure 2 Access Door 26

Figure 3A Studs For “Single Layer” Lining 27Figure 3A Studs For “Single Layer” Lining 27

Figure 3B “Single Layer” Linings 28Figure 3B “Single Layer” Linings 28

Figure 3C Studs And Anchors For Dual Layer Lining 29Figure 3C Studs And Anchors For Dual Layer Lining 29

Figure 4 Anchor Patterns For Castables 30Figure 4 Anchor Patterns For Castables 30

Figure 5 Wire Mesh Anchor Spacing For Stacks And Round Ducts 31Figure 5 Wire Mesh Anchor Spacing For Stacks And Round Ducts 31

Figure 6 Anchor Tie Back For Brick Lining 32Figure 6 Anchor Tie Back For Brick Lining 32

Figure 7A & B Anchor Pattern And Spacing For Compression & Lap Joints of

Ceramic Fiber Blanket 33Ceramic Fiber Blanket 33

Figure 8 Observation Door Detail 34Figure 8 Observation Door Detail 34

Figure 9 Typical Panel Joint 34Figure 9 Typical Panel Joint 34

Figure 10 Repair of Castable Linings 35Figure 10 Repair of Castable Linings 35

SCOPE

2.0 REFERENCES

The latest edition of the following publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices EP 11–1–1 Internal Insulating and Refractory Lining
EP 11–1–2 DS Fired Heater Refractory Data Sheet
EP 11–1–2C Fired Heater Refractory Inspection Checklist
ASTM Standards
C27 Fireclay and High Alumina Refractory Brick C113 Reheat Change of Refractory Brick
C133 Cold Crush Strength and Modulus of Rupture Refractory Bricks and Shapes C155 Classification for Insulating Firebrick
C201 Thermal Conductivity of Refractories C612 Mineral Fiber Block and Board Insulation
C860 Practices for Determining Consistency in Refractory Concrete
C892 High Temperature Fiber Blanket Thermal Insulation
SSPC Standards
SP6 Commercial Blast Cleaning

3.0

3.1

3.2

3.3

3.4

3.5

3.6

3.7

3.8

4.0

5.0

5.1

5.2

6.0

6.1

6.2

6.3

DEFINITIONS

IFB - Insulating Fire Brick

Inspector - A Inflection Point Engineering, LLC appointed engineer or inspector. Owner - Inflection Point Engineering, LLC

Owner’s Engineer - A Inflection Point Engineering, LLC appointed engineer.

Refractory Class: Light Weight - materials having an installed fired density of 75 pcf or less.

Refractory Class: Medium Weight - materials having an installed fired density greater than 75 pcf and less than, or equal to, 120 pcf.

Refractory Class: Heavy Weight - materials having an installed fired density greater than 120 pcf and less than, or equal to, 150 pcf.

Refractory Class: Dense - materials having an installed fired density greater than 150 pcf.

JOB SPECIFICATIONS

IPE shall issue specific requirements for refractory lining of a particular piece of equipment. This shall include type of refractory system, thickness, materials, method of refractory support and process conditions. For repair or replacement of refractory the job specification shall define the extent of refractory removal, cleaning, etc. which is required. Plant safety rules will be included as necessary.

CONTRACTOR SPECIFICATION

(*)The lining contractor is expected to install refractory in strict accord with manufacturers’ recommendations and the more general requirements of this practice. Conflicts will be resolved

by Owner’s Engineer.

Prior to application, the lining contractor must prepare a written supplemental specification and obtain approval of both the Owner’s Engineer and refractory supplier. The supplemental specifications must cover the installer’s application procedures and include specific requirements for mixing, applying, curing, etc.

DOCUMENTATION

All material properties shall be tested to ASTM Standards. Any deviations shall be reported to Owner’s Engineer.

Manufacturer’s data sheets showing gunned physical properties shall be supplied for all products to be pneumatically applied.

Bid Stage : The following information shall be supplied at the bid stage to assure complete evaluation:

DESIGN

ANCHORS

SURFACE PREPARATION

REFRACTORY HANDLING AND SHIPMENT

BLOCK INSULATION

BRICK LININGS

CERAMIC FIBER LININGS

CASTABLE LININGS

FIBER ADDITIONS

INSTALLATION AND CURING OF CASTABLES

REPAIR OF DEFECTIVE AREAS

DRYOUT

After curing, the initial dryout heating of new linings, or old linings which have been water soaked, shall comply with the following requirements:

INSPECTION AND TESTING

DRYOUT IS NOT PERMITTED UNTIL TEST RESULTS ARE APPROVED.

GUARANTEE

21.0 TABLES

TABLE 1

ANCHOR DESIGN TEMPERATURE

Maximum Permissible Temperature of Anchor(1) Acceptable Materials(2), (3)
1400°F 18 Cr 8 Ni (Type 304)
1700°F 25 Cr 20 Ni (Type 310)
1900°F RA330
2000°F Inconel 601
Above 2000°F Ceramic

NOTES:

TABLE 2 ANCHOR SPACING

Linings 3 inches or greater Spacing (1), (2), (3)
Walls, Cylinders 12 inches max. - 2 times thickness
Roofs, Slopes 9 inches max. - 2 times thickness
Arches 6 inches
Floors 24 inches max. - 4 times thickness

NOTES:

TABLE 3

CASING COATING REQUIREMENTS BASED ON FUEL’S SULFUR CONTENT

< 10 ppm < 10 ppm
< 0.5 wt%
 0.5 wt %
< 1.0 wt %
 1.0 wt %
Brick/ Block No Coating Required No Coating Required Casing Coating Required
(Sect. 7.0)
Do not use Brick/ Block (Sect. 11.0)
Ceramic Fiber No Coating Required Casing Coating Required
(Sect. 13.0)
Casing Coating Required Plus Vapor Barrier
(Sect. 13.0)
Casing Coating Required Plus Vapor Barrier
(Sect. 13.0)
Castable No Coating Required No Coating Required Casing Coating Required
(Sect. 7.0)
Casing Coating Required (Sect. 7.0)

TABLE 4 SAMPLE FREQUENCY

Material Order Size (tons) Tons Per Sample
Firebrick Any 25
Insulating Firebrick Any 25
Refractory Fiber Any No testing

NOTE:

Castable - One (1) sample per installer per shift for each different material.

TABLE 5

LIMITS OF RANGE OF ACCEPTABLE RESULTS

Property Average of 3 Average of 3 Individual Specimen Individual Specimen
Property Minimum Maximum Minimum Maximum
Density

Strength
95% Specified Density
95% Specified
Strength
105% Specified Density
None
90% Specified Density
90% Specified
Strength
110% Specified Density
None

NOTES:

TABLE 6 DOCUMENTATION REQUIREMENTS

FOR FIRED HEATER REFRACTORY PER EP 11–1–2

Item Description Format As–Built
1 All material properties shall be tested to ASTM Standards. Any deviations shall be reported to Owner’s Engineer. CALS G4 TIFF
(Compressed)
Yes
2 Data sheets showing gunned physical properties shall be supplied for all products to be pneumatically applied. CALS G4 TIFF
(Compressed)
Yes
3 Bid Stage: The information in the attached data sheets shall be supplied at the bid stage to assure complete evaluation. CALS G4 TIFF
(Compressed)
Yes
4 Final Design Approval Stage: The following information shall be supplied for approval by Owner’s Engineer for all final lining designs (i.e., after the order is placed).
Data Sheets.
Any changes from proposal information.
Refractory brand specified on drawings or proposed by the installer.
Steel fiber reinforced refractory (if applicable).
Name and telephone number of reference contacts at plants for whom the refractory installer, within the past 2 (two) years, has applied the type of refractory covered by this project.
Shipping and handling procedures for all refractory lined equipment and component parts shall be submitted for approval of Owner’s Engineer. Sufficient detail, including shipping supports, shall be provided to show that the parts will not be damaged by the usual handling and weather to be expected in transit and at the erection site.
CALS G4 TIFF
(Compressed)
Yes
5 Final Records: Per Data Sheets. CALS G4 TIFF
(Compressed)
Yes
6 CONTRACTOR SPECIFICATION
The lining contractor is expected to install refractory in strict accord with manufacturers’ recommendations and the more general requirements of this practice. Conflicts will be resolved by Owner’s Engineer.
CALS G4 TIFF
(Compressed)
Yes
7 Prior to application, the lining contractor must prepare a written supplemental specification and obtain approval of both the Owner’s Engineer and the refractory supplier. The supplemental specifications must cover the installer’s application procedures and include specific requirements for mixing, applying, curing, etc. CALS G4 TIFF
(Compressed)
Yes

22.0 FIGURES

FIGURE 1 NOSE DETAIL

Figure

Figure

Figure

Figure

Figure

Alloy Support Ledge 12 In. Min. Length Pieces

Ceramic Fiber Expansion Joint

FIGURE 2 ACCESS DOOR 3

Figure

FIGURE 3A

STUDS FOR “SINGLE LAYER” LINING

Figure

Figure

Figure

Figure

FIGURE 3B “SINGLE LAYER” LININGS

Figure

FIGURE 3C

STUDS AND ANCHORS FOR DUAL LAYER LINING

Figure

FIGURE 4

ANCHOR PATTERNS FOR CASTABLES

Figure

Figure

FIGURE 5

WIRE MESH ANCHOR SPACING FOR STACKS AND ROUND DUCTS

Figure

FIGURE 6

ANCHOR TIE BACK FOR BRICK LINING

Figure

FIGURE 7A & B

ANCHOR PATTERN AND SPACING FOR COMPRESSION & LAP JOINTS OF CERAMIC FIBER BLANKET

Figure

FIGURE 8 OBSERVATION DOOR DETAIL

Figure

FIGURE 10

REPAIR OF CASTABLE LININGS

Figure

Figure

Plate

Old Insulation

NOTES: