Inflection Point Engineering Section 6 — Rotating Equipment

General Purpose Lube Oil Systems

IPE Engineering Practice IPE-EP-6-9-2

Document number: IPE-EP-6-9-2 · Section: 6 — Rotating Equipment

GENERAL

Terms used in this Practice are defined as follows.

STANDARDS AND PUBLICATIONS

Engineering Practices
EP 1-1-3 Deviations to Engineering Practices EP 5-6-2 Piping for Rotating Equipment
EP 6-3-1 General Purpose Steam Turbines
EP 6-7-1 Special Requirements for Rotating Equipment
EP 6-8-1 Field Storage and Installation of Rotating Equipment
EP 8-1-2 TEMA Shell and Tube Heat Exchangers for Non-Process Services EP 12-1-1 Control Systems
EP 12-2-1 Control Systems Installations
EP 13-3-1 Induction Motors 500 HP and Below
EP 13-13-1 Electrical Standards for Packaged Equipment
ANSI Standards
Y14.2M Line Conventions and Lettering
API Standards
Std 676 Positive Displacement Pumps - Rotary
ASME Standards
B31.3 Chemical Plant and Petroleum Refinery Piping
Boiler & Pressure Vessel Code, Section V, "Nondestructive Examination"; Section VIII, "Pressure Vessels", Division 1 and 2;
Section IX, "Welding and Brazing Qualifications"
AWS Standards
D1.1 Structural Welding Code - Steel

BASIC DESIGN

EP 6-8-1. This inspection shall be witnessed by 's Inspector

2.6 Filters

2.6.1

2.6.2

2.6.3

2.6.4

2.6.5

2.6.6

2.6.7

2.6.8

2.6.9

2.7

2.7.1

2.7.2

2.7.3

2.7.4

2.7.5

Twin full-flow filters located downstream of the oil cooler and piped in a parallel arrangement using a continuous-flow transfer valve shall be provided.

(*) Filters shall have replaceable elements or cartridges with filtration of 10 microns nominal or finer, unless otherwise agreed to by . Filter cartridge materials shall be corrosion resistant. Metal mesh or sintered-metal filter elements are not acceptable.

Filters that have covers weighing more than 35 pounds shall be equipped with cover lifters.

When tops of the filters are more than 4 feet above the console base, the vendor shall provide an elevated deck to facilitate their service and maintenance.

Filters shall not be equipped with relief valves or other valves that can allow bypass of unfiltered oil around the filter elements.

Valved vents and clean- and dirty-side valved drain connections shall be furnished. The dirty- side connections shall be located lower in the housing than the filter elements or cartridge support bases.

Filter cases and heads shall be suitable for operation at a pressure not less than the relief valve setting of the oil pumps.

Oil filter design shall incorporate the following features:

The pressure drop for clean filter elements or cartridges shall not exceed 5 psi at an operating temperature of 100oF and normal flow. Elements or cartridges shall have a minimum collapsing differential pressure of 70 psi.

Transfer Valves

Transfer valves shall have steel bodies. Valve plugs or balls shall be made of stainless steel.

Transfer valves shall be designed so that, if the internal valve mechanisms fail, both flow paths will not be blocked.

Transfer valves shall be equipped with an indicator showing the flow path to help positively identify which filter or cooler is being used.

INSTRUMENTATION, CONTROL, AND ELECTRICAL SYSTEMS

3.2

3.2.1

3.2.2

3.2.3

3.2.4

3.2.5

3.2.6

3.3

3.3.1

3.3.2

3.3.3

3.3.4

Individual tubes or groups of individual tubes shall be continuously supported in conduit or angle iron. Wiring or attaching to a pipe is NOT acceptable.

Each instrument shall be permanently tagged with the item number and service. Teflon tape shall not be used; however, Teflon paste compounds may be used.

Oil heaters shall have thermostats set to limit oil temperature in the reservoir to the value recommended by the equipment vendor, normally 120oF or less.

Instrument Gauge Boards and Panels

The instruments on the gauge board and panel shall be individually labeled and clearly visible to the operator from the driver control point.

Gauge boards and panels shall be completely piped and wired, requiring only connections to the Purchaser's external piping and wiring circuits. When more than one wiring point is required on a unit for controls or instrumentation, wiring to each switch or instrument shall be provided from terminal posts in a single terminal box which is mounted on the unit or its base, if any.

(*) Instrument connections shall terminate at locations specified by the Purchaser.

All wiring shall be installed in metal conduit or enclosures. All leads and posts on terminal strips, switches, and instruments shall be tagged for identification purposes.

Alarms and Shutdowns

(*) As a minimum, the vendor shall furnish and mount the alarm and shutdown contacts as specified on the data sheets.

(*) Switches, control devices, and annunciator display units shall be furnished and mounted by the vendor as specified by the Purchaser.

(*) Unless otherwise specified, each alarm switch and each shutdown switch shall be furnished in a separate housing located to facilitate inspection and maintenance. Switch settings shall not be adjusted from outside the housing.

Alarm and shutdown devices shall function directly, not indirectly through a control panel, and shall be suitable for operation on both alternating current (AC) and direct current (DC).

EP 13-14-1.

INSPECTION, TESTING, AND PREPARATION FOR SHIPMENT

(4) hours.

4.4

4.4.1

4.4.2

4.4.3

4.4.4

4.4.5

4.4.6

0.004 inch and a 0.006 inch opening. The particles' greatest dimension shall not exceed

0.010 inch, and the particles shall be randomly distributed on the screen.

Preparation for Shipment

As a minimum, equipment shall be suitably prepared in accordance to the requirements specified in EP 6-7-1.

Lifting points and lifting lugs shall be clearly identified.

Exposed shaft and shaft couplings shall be wrapped with waterproof, moldable waxed cloth or vapor-phase inhibitor paper. The seams shall be sealed with oil-proof adhesive.

Each filter shall be shipped with clean elements installed.

The vendor shall provide the Purchaser with instructions necessary to preserve the integrity of the storage preparation after the oil system is received at the job site and before startup.

Components shipped with mounted pre-assembled piping, tubing, or wiring shall comply with the requirements of the Occupational Safety and Health Administration (OSHA).

VENDOR DATA

The vendor's proposal shall include, but not be limited to, the following:

GUARANTEE AND WARRANTY

(*) The equipment package shall be guaranteed for satisfactory performance, both mechanically and hydraulically, at startup, shutdown and all operating conditions as specified on the data sheets.

The entire equipment package shall be warranted by the vendor against defective materials, designs, and /or workmanship for one year after being placed in service or eighteen months after shipment, whichever comes first. The vendor shall be responsible for promptly correcting any of these problems at no cost to .

7.0 TABLES

TABLE 1

MAXIMUM ALLOWABLE NUMBER OF PARTICLES

Nominal Pipe Size (Inches) Schedule 40 Schedule 80 or More
< 1 6 5
1 to 1-1/2 15 10
2 20 20
3 45 40
4 80 70
6 180 160

8.0 FIGURES

FIGURE 1

TYPICAL LUBE OIL SYSTEM SCHEMATIC

Figure

FIGURE 2

LUBE OIL SYSTEM VENDOR DRAWING AND DATA REQUIREMENTS

FOR

SITE

PURCHASE ORDER NO. DATE

REQUISITION NO. DATE

SERVICE INQUIRY NO. DATE

ITEM NO. PAGE OF BY

REVISION UNIT NO. REQUIRED

Proposal a

DESCRIPTION
1. Certified dimensional outline drawing and list of connections.
2. Cross-sectional drawings and bills of materials.
3. Lube-oil schematic and bill of materials, including component sizing criteria.
4. Lube-oil arrangement drawing and list of connections.
5. Lube-oil component drawings and data.
6. Electrical and instrumentation schematics and bill of materials.
7. Electrical and instrumentation arrangement drawing and list of connections.
8. Console test agenda.
9. Weld procedures.
10. Certified hydrostatic test records.
11. Certified operational test logs.
12. As-built data sheets.
13. Operating and maintenance manuals.
14. Spare parts recommendation and price list.

Bidder shall furnish copies of data for all items indicated by an

a Proposal drawings and data do not have to be certified or as built. Typical data shall be clearly identified as such.

b Purchaser will indicate in this column the desired time frame for submission of materials using the nomenclature given at the end of the form.

c Bidder shall complete these two columns to reflect his actual distribution schedule and include this form with his proposal.