Inflection Point Engineering Section 4 — Structures and Foundations

Structural Steel Construction

IPE Engineering Practice IPE-EP-4-5-2

Document number: IPE-EP-4-5-2 · Section: 4 — Structures and Foundations

1.0 SCOPE 5

2.0 REFERENCES 5

3.0 DEFINITIONS 6

4.0 FOAM SYSTEM APPLICATIONS 8

4.1 Philosophy 8

4.2 Process Area Protection 9

4.3 Atmospheric Storage Tank Protection 9

4.4 Loading/Unloading Rack Protection 9

4.5 LNG Spill/Fire Protection 9

4.6 Pier and Wharf Protection 9

5.0 GENERAL DESIGN AND INSTALLATION REQUIREMENTS 9

5.1 Design and Installation Responsibility 9

5.2 Proposal Requirements 10

5.3 Design Development and Documentation 10

5.4 General Design Considerations 11

5.5 System Operation 14

5.6 Equipment Selection 14

5.7 Design Considerations for Specific Applications 15

6.0 PORTABLE AND MOBILE FOAM EQUIPMENT 16

6.1 Portable Foam Equipment 16

6.2 Mobile Foam Equipment 17

7.0 SUBSURFACE INJECTION SYSTEMS 17

8.0 FOAM CHAMBER SYSTEMS 18

8.1 Fixed Roof Tank Protection 18

8.2 Floating Roof Tank Protection 18

9.0 CATENARY SYSTEMS 19

9.1 Design 19

9.2 Installation 20

10.0 THROUGH–THE–TANK SYSTEMS 21

10.1 Design 21

10.2 Installation 21

11.0 TANK STANDPIPE SYSTEMS 21

11.1 Design 21

11.2 Installation 22

12.0 FOAM–WATER SPRAY SYSTEMS 22

12.1 Design 22

12.2 Installation 23

13.0 HIGH EXPANSION FOAM SYSTEMS 23

14.0 ACCEPTANCE TESTING 23

15.0 SYSTEM MAINTENANCE AND PERIODIC TESTING 23

15.1 General 23

15.2 Inspections 24

15.3 System Tests 24

15.4 Maintenance 24

16.0 TABLES 26

Table 1 Foam Requirements for Atmospheric Storage Tanks - Class I, II and IIIA Liquids 24

Table 2 Suitability of Types of Foam Concentrates 25

Table 3 Density, Water and Foam Concentrate Supply Requirements for Foam Systems 26

Table 4 Foam Requirements for Atmospheric Storage Tanks - Class I, II or IIIA Liquids 27

Table 5 Flush Flow Rates 28

Table 6 Piping Flushing Rates 28

Table 7 Documentation Requirements for Fire Protection from EP 3–5–4 28

17.0 FIGURES 29

Figure 1 Process Unit Spill Area Calculation (Ditch Drains) 29

Figure 2 Catenary Foam System 30

Figure 3 Through The Tank Foam System (Semifixed System). 31

Figure 4 Manual Protection – Foam Standpipe. 32

SCOPE

2.0 REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

Engineering Practices
EP 1–1–3 Deviations to Engineering Practices EP 2–5–2 Documentation Format Requirements
EP 3–5–2 Firewater Systems
EP 3–5–3 Fixed Water Spray Fire Protection Systems EP 3–5–6 Fire Protection of Piers and Wharves
EP 5–1–1 General Piping Design
EP 9–1–1 Atmospheric Storage Tanks EP 10–3–1 Shop Painting
EP 10–3–2 Field Painting
EP 10–3–3 Corrosion Protection for Underground Pipe EP 13–1–1 Power System Design Practices
EP 14–1–1 Winterization
ASME/ANSI Standards
B1.1 Unified Inch Screw Threads B2.2 Dryseal Pipe Threads
B16.5 Steel Pipe Flanges, Flanged Valves and Fittings
ASME Code
B31.3 Process Piping
API Publication
Publ 2021 Guide for Fighting Fires in and Around Flammable and Combustible Liquid Atmospheric Storage Tanks

STANDARDS AND PUBLICATIONS (CONT.)

NFPA Codes
11 Low Expansion Foam and Combined Agent Systems 11A Medium and High Expansion Foam Systems
11C Mobile Foam Apparatus
16 Deluge Foam–Water Sprinkler and Spray Systems
30 Flammable and Combustible Liquids Code 72E Automatic Fire Detectors
321 Basic Classification of Flammable and Combustible Liquids 1961 Fire Hose
Military Specification
MIL–F–24385C Fire Extinguishing Agents Aqueous Film Forming (ASFF Liquid Concentrate Fresh and Seawater)

DEFINITIONS

FOAM SYSTEM APPLICATIONS

This Section of the Practice describes the basic philosophy behind foam fire protection and when foam fire protection systems are required. The requirements for foam fire protection systems shall also comply with all appropriate federal and local jurisdictional requirements. In case of conflicts, the more stringent requirement shall apply.

A fixed foam–water spray system shall be installed on loading or unloading racks where Class I products are loaded or unloaded or where switch loading is practiced.

A high–expansion foam system shall be installed in retention/vaporization areas of LNG storage facilities to reduce the rate of vaporization of spilled LNG and reduce the intensity of an LNG fire.

Fixed ground level and elevated foam–water monitors and foam–water spray systems are used for the protection of piers and wharves where liquid hydrocarbons are handled. See EP 3–5–6 for a detailed discussion and recommendations for use of foam at these facilities.

GENERAL DESIGN AND INSTALLATION REQUIREMENTS

The successful vendor shall perform a detailed system design and provide the following design documentation for review and approval prior to system installation:

Foam concentrates selected for use shall be listed by Underwriter’s Laboratory as a foam liquid concentrate, aqueous film forming foam liquid concentrate, or high expansion foam liquid concentrate as appropriate, and shall be used within the constraints of its listing.

Inlet connections shall be corrosion–resistant, provided with appropriate plugs or caps, and installed in accordance with the requirements in Table 3.

Water inlet connections shall not be provided on fixed foam systems or foam–water spray systems, unless required by the authority having jurisdiction (AHJ). If required by the AHJ, the water inlet connection shall be upstream of the proportioning equipment.

A means shall be provided to allow atmospheric foam concentrate tanks to be refilled without interrupting foam production.

5.5.2 Semi–fixed systems, mobile and portable equipment require varying amounts of manpower for set–up and operation. Installation of these systems or use of this equipment shall be limited to locations where adequate trained manpower is available. When the appropriate level of trained manpower is not available, a fixed system shall be provided.

Foam proportioning, aspirating, and discharge devices shall be designed for the intended use and listed by Underwriter’s Laboratory or approved by Factory Mutual.

Open air process units and other plant areas where flammable or combustible liquids are present shall be protected by mobile and/or portable foam equipment in accordance with this section.

Aspill = D2 + Aditch, where: Aspill is the spill area

D is the distance between the center of the unit and the closest drainage ditch, and

Aditch is the area of the drainage ditch between the nearest fire seals.

Foam–water spray systems for loading and unloading racks shall be designed based on a spill covering an area extending 5 feet in all directions from the edge of the tank trucks or cars serviced by the rack. When drainage and/or containment is provided, the entire containment or drainage area for the rack shall be protected, if it exceeds the area required above. When no drainage or containment is provided, the spray shall be arranged to discharge over the area required above, but the application density and quantity of foam required shall be based on a spill area that extends 20 feet in all directions from the edge of the tank trucks or cars serviced by the rack.

PORTABLE AND MOBILE FOAM EQUIPMENT

Portable foam equipment shall comply with the requirements of NFPA 11 and the requirements of this Section.

Foam monitors shall meet the requirements of NFPA 11 and the requirements of this Section.

6.2 Mobile Foam Equipment

Mobile foam equipment shall meet the requirements of NFPA 11C.

SUBSURFACE INJECTION SYSTEMS

FOAM CHAMBER SYSTEMS

Foam chamber systems shall be installed for storage tank protection as indicated in Table 4. The systems shall be designed to provide the density of fluoroprotein foam required in Table 3 to the protected area for the time stated in Table 3. In addition, adequate foam supplies and foam producing equipment shall be provided to support supplemental foam hose streams, as specified in NFPA 11, Chapter 3.

In order to protect the foam solution piping from the upward force and shock of a tank roof rupture one of the following methods shall be used:

CATENARY SYSTEMS

THROUGH–THE–TANK SYSTEMS

TANK STANDPIPE SYSTEMS

FOAM–WATER SPRAY SYSTEMS

Fixed foam–water spray systems provided for protection of loading/unloading racks or enclosed process areas shall be designed in accordance with the requirements of NFPA 16 and NFPA

11. For loading/unloading racks, the required discharge density and duration shall be in accordance with Table 3. The system shall be arranged to shut down all loading/unloading pumps and valves to the affected rack.

Foam–water spray systems shall be installed in accordance with NFPA 16 and the EP 3–5–3.

HIGH EXPANSION FOAM SYSTEMS

The following design criteria shall be used for high expansion foam protection of LNG spill retention basins, pump pits, and other confined areas where leakage of LNG may occur in LNG storage facilities:

ACCEPTANCE TESTING

SYSTEM MAINTENANCE AND PERIODIC TESTING

Inspections of fixed, semi–fixed, portable and mobile foam systems to detect obvious conditions affecting system effectiveness are recommended on a daily, weekly, and annual basis. Each recommended inspection routine has specific objectives to determine if the system is in operating readiness.

Routine tests during the life of the system shall be compared with results during acceptance tests to gauge potential deterioration of system performance and operability. Annual tests provide assurance that actuating systems will operate when required.

Properly performed annual maintenance is required to prevent failures of the systems during emergencies. The following annual maintenance sEPs shall be followed:

16.0 TABLES

TABLE 1

FOAM REQUIREMENTS FOR ATMOSPHERIC STORAGE TANKS - CLASS I, II AND IIIA LIQUIDS

Tank Type Tank Diameter Foam Protection Requirements
Cone Roof 60 feet or less Portable and/or mobile equipment for full tank
surface area.
Cone Roof > 60 Feet Fixed or semi–fixed system designed for full tank
surface area.
Cone Roof with Metal
Pan Type Cover (1)
All Fixed or semi–fixed system for protection of the
full tank surface area.
Cone Roof with
combustible cover (1)
All Fixed or semi–fixed system for protection of the full
tank surface area.
Cone roof with thin steel skin cover
on floats
All None required, unless by local code. If required,
provide a fixed or semi–fixed system for rim seal protection.
Cone roof with thin skin aluminum cover on floats or aluminum
honeycomb cover
All None required, unless by local code. If required, provide a fixed or semi–fixed system or full surface protection.
Floating Roof < 100 Feet Portable and/or mobile equipment for rim seal protection.
Floating Roof 100–120 Feet Portable and mobile or fixed equipment for rim
seal protection.
Floating Roof > 120 Feet Fixed or semi–fixed system for rim seal protection.
Covered Floating Roof All None required, unless by local code. If required, provide a fixed or semi–fixed system for rim
seal protection.

NOTE:

(1) This design is not permitted by NPFA 30 and should not be considered for new installations

TABLE 2

SUITABILITY OF TYPES OF FOAM CONCENTRATES

Fire/Spill Situation Type of Foam Concentrate Type of Foam Concentrate Type of Foam Concentrate Type of Foam Concentrate Type of Foam Concentrate
Fire/Spill Situation Fluoroprotein AFFF FFFP Alcohol Resistant High Expansion
Process Area Spill Fire A P A P N.S.
Storage tank fire – Surface application (up to 10% polar
solvent content)
P N.S. N.S. A N.S.
Storage tank fire – Subsurface Application (up to 10% polar solvent content) P N.S. N.S. N.S. N.S.
Storage tank fire – Surface Application (> 10% polar solvent content) N.S. N.S. N.S. P N.S.
Storage tank - Subsurface
Application (> 10% polar solvent content)
N.S. N.S. N.S. N.S. N.S.
Loading rack fire – (< 10% polar solvents) A P A P N.S.
Loading rack fire – (> 10% polar solvents) N.S. N.S. N.S. P N.S.
LNG spill or fire N.S. N.S. N.S. N.S. P

P = Preferred; A = Acceptable; N.S. = Not Suitable

TABLE 3

DENSITY, WATER AND FOAM CONCENTRATE SUPPLY REQUIREMENTS FOR FOAM SYSTEMS (HYDROCARBON LIQUIDS MAX. POLAR SOLVENT CONTENT OF 10%)

Hazard Protected Density Required (GPM/FT) Density Required (GPM/FT) Minimum Water and From Concentrate Supply Required
(duration in minutes)
Hazard Protected Fluoroprotein AFFF or FFFP Minimum Water and From Concentrate Supply Required
(duration in minutes)
Open Process Area Spill fire
(Portable Equipment)
0.16 0.10 15
Enclosed Process Area Spill Fire
(Foam–Water Spray System)
0.16 0.10 15
Fixed Roof Storage Tank
(Over–the–Top With Fixed Outlets)
0.10 N.A. 30 (Class II or III liquids)


55 (Class I or crude oil)
Fixed Roof Storage Tank
(Subjection Injection)
0.10 N.A. 30 (Class II or III liquids)


55 (Class I or crude oil)
Fixed and Floating Roof Storage Tank (Portable Discharge Devices) 0.16 N.A. 50 (Class II or III liquids) 65 (Class I or crude oil)
Floating Roof Storage Tanks
(Fixed above seal discharge devices foam dam)
0.30 N.A. 20
Loading Rack (Foam–Water Spray Systems) 0.16 0.16 10

TABLE 4

FOAM REQUIREMENTS FOR ATMOSPHERIC STORAGE TANKS - CLASS I, II OR IIIA LIQUIDS

Tank Type Tank Diameter Foam Protection Requirements
Cone Roof 60 Feet or less Mobile or portable foam monitors.
Cone Roof Between 60 and
200 Feet
Subsurface injection for hydrocarbon liquids. Foam chambers for foam
destructive liquids. Fixed or semi–fixed system.
Cone Roof > 200 Feet Subsurface or Subsurface with foam chambers.
Fixed or semi–fixed system.
Cone Roof with Metal Pan Type cover All Fixed or semi–fixed foam chamber system
for protection of the full tank surface area.
Cone Roof with combustible cover All Fixed or semi–fixed foam chamber system for
protection of the full tank surface area.
Cone roof with thin steel skin cover on floats All None required, unless by local code.
If provided, a fixed or semi–fixed foam chamber system for rim seal protection should
be installed.
Cone roof with thin skin aluminum cover on floats or aluminum honeycomb cover All None required, unless by local code.
If provided, a fixed or semi–fixed foam
chamber system for full surface protection should be Installed.
Open Top Floating Roof 100 Feet Portable foam hose lines for rim fire protection.
Open Top Floating Roof 100–120 Feet Portable hose line from tank standpipe for
rim fire protection (Figure 2). (1)
Open Top Floating Roof > 150 Feet Fixed or semi–fixed catenary, through–the–tank,
or foam chamber system for rim seal protection.
Covered Floating Roof All None required, unless by local code.
If provided, a fixed or semi–fixed through–the tank or foam chamber system for rim seal
protection should be installed.

NOTE:

(1) A fixed or semi–fixed catenary, through–the tank or foam chamber system for rim seal protection should be provided If the tank does not have a wind girder with hand rails.

TABLE 5 FLUSH FLOW RATES

Nominal Pipe Size (in.) Flow (gpm) Flow (L/min)
4 390 1476
6 880 3331
8 1560 5905
10 2440 9235
12 3520 13323

TABLE 6

Piping FLUSHING RATES

Nominal Pipe Size (in.) Flow (gpm) Flow (L/min)
4 390 1476
6 880 3331
8 1560 5905
10 2440 9235
12 3520 13323

TABLE 7

DOCUMENTATION REQUIREMENTS FOR FIRE PROTECTION FROM EP 3–5–4

Item Description Format As–Built
1 Documentation of the fire protection engineering analysis of heated tanks containing Class IIIB liquids. See EP 2–5–2 N/A
2 Complete vendor proposal. See EP 2–5–2 Yes
3 Detailed system design. See EP 2–5–2 Yes
4 Written statement of final systems testing. See EP 2–5–2 N/A

17.0 FIGURES

FIGURE 1

PROCESS UNIT SPILL AREA CALCULATION (DITCH RAINS)

EXAMPLE CALCULATIONS D=90 FT.

A ditch = 2 (2T.) = 5,500 SQ FT.

A spill = D2 + A ditch = (90 FT )2 + 5,500 SQ FT. = 13,600 SQ FT.

Figure

Figure

Figure