Section 4 — Structures and Foundations
Concrete Design
IPE Engineering Practice IPE-EP-4-3-1
Document number: IPE-EP-4-3-1 · Section: 4 — Structures and Foundations
SCOPE
- This Practice covers requirements for the design of reinforced concrete for foundations, buildings, and all other structures.
- Requirements for concrete construction and concrete reinforcement fabrication are covered in EP 4-3-2 and EP 4-3-3, respectively.
- Any deviation to this Practice must be approved by the procedure described in EP 1-1-3.
- An asterisk (*) indicates that a decision or approval by the Owner or the Owner's Engineer is required, or that additional information is furnished by the Purchaser.
- A revision bar indicates all changes made to this Revision.
- Documentation required in accordance with this Practice is given in Table 2.
2.0 REFERENCES
The latest edition of the following Standards and Publications are referenced herein.
STANDARDS AND PUBLICATIONS
| IPE Engineering Practices |
EP 1-1-3 Deviations to IPE Engineering Practices EP 4-1-1 Design Criteria and Loads for Structures EP 4-2-3 Reinforced Concrete Foundations EP 4-3-2 Concrete Construction Requirements EP 4-3-3 Concrete Reinforcement Fabrication EP 4-4-1 Roadways and Paving |
| ACI Standard |
211 Standard Practice for Selecting Proportions for Concrete 313 Recommended Practice for Design and Construction of Concrete Silos, Bins and Bunkers for Storing Granular Materials 315 Manual of Standard Practice for Detailing Reinforced Concrete Structures 318 Building Code Requirements for Reinforced Concrete |
| ASTM Standards |
A82 Cold-Drawn Steel Wire for Concrete Reinforcement A185 Welded Steel Wire Fabric for Concrete Reinforcement |
STANDARDS AND PUBLICATIONS (CONTINUED)
| ASTM Standards (Continued) |
A615 Deformed and Plain Billet Steel Bars for Concrete Reinforcement C31 Making and Curing Concrete Test Specimens in the Field C33 Concrete Aggregates C109 Test Method for Compressive Strength of Hydraulic Cement Mortars C150 Portland Cement C192 Making and Curing Concrete Test Specimens in the Laboratory C260 Air-Entraining Admixtures for Concrete C494 Chemical Admixtures for Concrete C618 Fly Ash and Raw or Calcined Natural Pozzolan for Use as a Mineral Admixture in Portland Cement Concrete |
| CRSI Practice |
| MSP-2-81 Manual of Standard Practice |
DEFINITIONS
- Contractor - Company or business that agrees to furnish materials or perform specified services at a specified price and/or rate to the Owner.
- Inspector - A Inflection Point Engineering, LLC appointed engineer or inspector.
- Manufacturer - The recipient of a direct or indirect purchase order for materials and/or equipment. In this context, a direct order is one issued to a manufacturer by a contractor or the Owner. An indirect order is one issued to a manufacturer by a vendor (recipient of a direct order) for materials, fabricated components, or subassemblies.
- Moderate Sulfate Service - 0.10 to 0.20% water soluble sulfate (SO4 ) in soils or 150 to 1,500 ppm sulfate (SO4 ) in solution.
- Non-Sulfate Service - Less than 0.10% water-soluble sulfate (SO4 ) in soils or less than 150 ppm sulfate (SO4 ) in solution.
- Owner - Inflection Point Engineering, LLC.
- Owner's Engineer - A Inflection Point Engineering, LLC appointed engineer.
- Purchaser - The party placing a direct purchase order. The purchaser is the Owner's designated representative.
- Severe Sulfate Service - 0.20 to 2.0% water-soluble sulfate (SO4 ) in soils or 1,500 to 10,000 ppm sulfate (SO4 ) in solution
MATERIALS
ACI 211 shall be consulted in the proportioning of concrete mixes.
- Cement
- (*)Unless otherwise specified by the Owner's Engineer, ASTM C150 Type I Portland cement shall be used in non-sulfate service. See Section 3.0 of this Practice.
- ASTM C150 Type II Portland cement shall be used in moderate sulfate service. See Section
3.0 of this Practice.
- ASTM C150 Type V Portland cement shall be used in severe sulfate service. See Section 3.0 of this Practice.
- (*)If greater than 2.0% water-soluble sulfate in soils or greater than 10,000 ppm sulfate in solution is present, pozzolan shall be added to Type V cement. The amount and type of pozzolan shall be determined by tests of the cement's sulfate resistance, and shall be approved by the Owner.
- (*)Type Ill, high-early strength concrete shall be used only when approved by the Owner's Engineer.
- (*)Admixtures shall be used only when specified by the Owner, and shall satisfy the additional requirements of this Paragraph.
- (*)Air-entraining admixtures shall conform to ASTM C260. The amount of air to be used in air- entrained concrete depends on many factors and shall be specified by the Owner.
- Water-reducing, retarding, accelerating and combination admixtures shall conform to ASTM C494.
- Fly ash or pozzolan used as admixtures shall conform to ASTM C618.
- Aggregate for concrete shall conform to ASTM C33 and the following requirements:
- (*)Fine aggregate shall be high-silica sand, unless otherwise approved by the Owner.
- (*)Coarse aggregate shall be crushed rock or siliceous gravel. Limestone shall not be used unless approved by the Owner. The Purchaser shall specify the size of aggregate.
- Water used in concrete shall be clean and free from injurious amounts of oils, acids, alkalis, salts, organic materials or other substances deleterious to concrete or carbon steel. Non- potable water shall not be used in concrete unless the following are satisfied:
- Proportioning of the concrete is based on mixes using water from the same source.
- Mortar test cubes made with the non-potable water and tested per ASTM C109 exhibit 7 and 28 day strengths of at least 90% of strengths of similar specimens made with potable water.
- (*)Dyes shall be added to concrete only when specified by the Purchaser. Type and amount of dye, when added, shall be specified by the Owner's Engineer.
- The contractor shall document all materials (cement, aggregate, and any admixtures) used in the mix, as well as the average compressive strength of the concrete.
- Metal Reinforcement for Concrete
- All materials shall be new and free from loose or flaky rust, mill scale, grease, oil, mud, or any other coating which would reduce or destroy the bond to concrete.
- (*)Metal reinforcement shall be Grade 60 deformed bars conforming to ASTM A615, unless otherwise specified.
- Plain steel wire for spiral reinforcement shall conform to ASTM A82 with a minimum yield strength of 70,000 psi.
- Welded plain wire fabric shall conform to ASTM A185 with a minimum yield strength of 65,000 psi.
- (*)Reinforcement supports shall be standard types and sizes given in Chapter 3 of CRSI MSP- 2-81. Unless otherwise specified by the Owner, materials shall be selected based on the three classes of protection given in CRSI MSP-2-81.
DESIGN
- Concrete design for building and pipe support structures shall be in accordance with ACI 318 and the additional requirements of this Practice.
- (*)Pre-stressed or post-tensioned concrete shall not be used unless approved by the Owner.
- The design of concrete silos, bins and bunkers for storing granular materials shall be in accordance with ACI 313 and the additional requirements of this Practice.
- The design of reinforced concrete foundations shall be in accordance with EP 4-2-3 and the additional requirements of this Practice.
- Concrete pavements shall be designed in accordance with EP 4-4-1 and the additional requirements of this Practice.
- (*)Concrete design details shall be prepared in accordance with ACI 315. Plan, elevation, and detail drawing required for the construction of a concrete structure shall be submitted to the Owner's Engineer.
- Design loads for concrete structures shall be in accordance with EP 4-1-1.
- (*)Unless otherwise specified by the Owner, concrete shall have a minimum compressive strength per Table 1. The values shown in Table 1 represent 28-day compressive strength of normal Portland cement concrete, or 7-day compressive strength of high-early strength concrete, as determined by tests on 6-inch diameter by 12-inch high cylinders per ASTM C192, ASTM C31 and EP 4-3-2.
- All steel shall be galvanized when surfaces will be exposed after the concrete is finished.
6.0 TABLES
TABLE 1
APPLICATION AND COMPRESSIVE STRENGTHS OF CONCRETE
| APPLICATION |
COMPRESSIVE STRENGTH psi |
| Prestressed piling exposed to sea water |
5,000 |
Prestressed and precast concrete structures Precast piling |
4,000 |
Precast pipe Precast concrete sills, copings, and all ornamental concrete Reinforced concrete chimneys Foundations for tanks in sulfuric acid service Concrete structures in continuous contact with sea water Reservoirs and separators |
3,500 |
Girders, beams, walls, slabs, piers, and columns Superstructure for docks and bridges Concrete structures over sea water Pipe supports Concrete for fireproofing Concrete on or below grade: such as footings, pile caps, tank foundations, tie beams, grade beams, anchor blocks, pump blocks, catch basins, manholes, sidewalks, and paving (1) Cast-in place piling (land use) (1) |
3,000 |
| Concrete for underground electrical (protective cover, etc.) |
2,000 |
Low-strength concrete for filling purposes where mass, rather than strength, is the principal requirement |
1,500 |
NOTE:
(1) Concrete exposed to moderate sulfate attack.
TABLE 2
DOCUMENTATION REQUIREMENTS FOR CONCRETE DESIGN PER EP 4-3-1
| Item |
Description |
Format |
As-Built |
| 1 |
Specification of materials used in concrete mixtures. |
Text |
N/A |
| 2 |
Plan, elevation and detail drawings required for the concrete structures. |
See EP 2-5-2 |
Yes |
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.
© 2026 Inflection Point Engineering, LLC. All rights reserved.