Inflection Point Engineering Section 3 — Process Safety & Loss Prevention

Firewater Systems

IPE Engineering Practice IPE-EP-3-5-2

Document number: IPE-EP-3-5-2 · Section: 3 — Process Safety & Loss Prevention

1.0 SCOPE 5

2.0 REFERENCES 5

3.0 DEFINITIONS 6

4.0 APPLICABILITY 7

4.1 Good Engineering Practice 7

4.2 Available Personnel 7

4.3 Federal and Local Requirements 7

4.4 Required Fire Fighting Facilities 7

4.5 Pre–Fire Plans 8

4.6 Summary of Provisions 8

5.0 FIREWATER SYSTEM SERVICE CONDITIONS 8

5.1 Design Basis 8

5.2 Largest Combined Firewater Demand 9

5.3 Process Unit Firewater Demand 9

5.4 Atmospheric Storage Tank Firewater Demand 9

5.5 Firewater Demand for Pressurized Storage 10

5.6 Auxiliary Requirements 10

5.7 Firewater Supply 10

5.8 Firewater Contamination 11

6.0 REQUIREMENTS FOR FIRE MAIN PRESSURES 11

6.1 Residual Pressure 11

6.2 Residual Pressure Considerations 11

7.0 FIRE PUMP DESIGN REQUIREMENTS 12

7.1 Firewater Pumping Capacity 12

7.2 Pump Type and Arrangement 12

7.3 Pump Size 13

7.4 Types of Drivers 13

7.5 Firewater Pressure Maintenance 14

7.6 Fire Pump Starting 15

7.7 Pump Enclosure 15

9.0 FIRE MAIN AND HYDRANTS ARRANGEMENTS 15

9.1 Fire Main Design 15

8.2 Fire Main Size and Rating 16

8.3 Fire Hydrant Locations and Sizes 17

9.0 MONITORS 19

9.1 General 19

9.2 Limitations and Location Guidelines 19

9.3 Water Monitors 19

9.4 Installation Requirements 19

9.5 Portable Monitors 20

9.6 Application 20

10.0 TABLES 21

TABLE 2 FIREWATER MONITORS 21

TABLE 3 FOAM/WATER MONITORS 22TABLE 3 FOAM/WATER MONITORS 22 Table 4 Documentation Requirements 22Table 4 Documentation Requirements 22

11.0 FIGURES 23

Figure 1 Firewater Pumping Capacity as a Function of Throughput 23

Figure 2 Fire Hydrant Guardrails Typical Arrangement 24

Figure 3A Wet Barrel Hydrants 6 In. and 8 In. 25

Figure 3B Wet Barrel Hydrants 4 In. 26

Figure 4 Typical Siting of Monitors 27

Figure 5 Monitor Guardrails Typical Arrangement 28

Figure 7 Typical Firewater System 30

SCOPE

2.0 REFERENCES

The latest edition of the following standards and publications are referred to herein.

STANDARDS AND PUBLICATIONS

IPE Engineering Practices
EP 1–1–3 Deviations to IPE Engineering Practices EP 6–3–1 General Purpose Steam Turbines
EP 6–3–2 Special Purpose Steam Turbines
EP 10–3–3 Corrosion Protection for Underground Pipe
API Recommended Practices
RP 2001 Fire Protection in Plants
NFPA Codes
No. 11 Low Expansion Foam and Combined Agent Systems No. 13 Installation of Sprinkler Systems
No. 15 Water Spray Fixed Systems
No. 20 Installation of Centrifugal Fire Pumps No. 24 Installation of Private Fire Service Mains
No. 30 Flammable and Combustible Liquids Code
No. 321 Basic Classification of Flammable and Combustible Liquids No. 1901 Pumper Fire Apparatus
No. 1963 Fire Hose Thread Connections

DEFINITIONS

APPLICABILITY

The requirements contained in this specification are minimum design requirements based on National Fire Protection Association (NFPA) codes, American Petroleum Institute (API) standards and good engineering practices. Key assumptions that form the basis for these standards are as follows:

Specification requirements are based on the assumption that process and equipment design follow good engineering practice, as defined by the IPE Engineering Practices and accepted industry practices. Where design or equipment is less than defined by good practice standards, firefighting facilities may need expansion after a fire protection engineering analysis of the risk involved. For example, this will occur when equipment spacing is less than adequate or when a control room is not blast resistant.

During an emergency, personnel are usually preoccupied with safe, timely equipment shutdown and minimal manpower is available to fight fires. The requirements of this specification are based on a minimum of plant operators being available for firefighting.

Recognized Federal and/or local codes and standards shall be followed unless the requirements of this specification are more stringent. If Federal and local requirements are more stringent, the requirements of this specification shall be followed with the written approval of the authority having jurisdiction.

FIREWATER SYSTEM SERVICE CONDITIONS

The largest–diameter cone roof tank may determine the maximum firewater requirement for a given tank farm and may dictate the plant firewater design capacity. NFPA 11 shall be used to determine firewater requirements for all types of atmospheric storage tanks.

A firewater source shall be provided from either an unlimited source, such as a natural body of water, a storage tank or reservoir. Storage tank or reservoir capacity shall be sized to provide a minimum of six hours continuous operation of the fire pumps at rated capacity. After the initial six hours of operation the water source must also be capable of supplying one half of the maximum pumping capacity for a minimum of twelve additional hours. This continuous supply is based upon shutting down all non-critical operations before the end of the six-hour time period.

Plant effluent shall not be used as a firewater source for fire fighting foams (protein, fluoroprotein, AFFF’S, alcohol types) when emulsion–breaking or anti–foaming compounds are used for water treatments. Firewater intakes shall be located so as to avoid contamination by plant effluent or sewage. Contaminated foam is not fire resistant and allows the foam blanket to break down when exposed to the heat of a fire.

REQUIREMENTS FOR FIRE MAIN PRESSURES

Fire main residual pressure shall be sufficient to satisfy pressure requirements for cooling streams, fog nozzle streams, and foam hose streams using pickup tubes. There must be sufficient pressure to supply fixed water spray systems, fixed monitors, and firewater needs at the highest plant elevation. Additional booster pumps may be used where unusual elevation changes are present on the site.

FIRE PUMP DESIGN REQUIREMENTS

An adequate number of fire pumps shall be provided to supply the total firewater pumping capacity as determined from Figure 1. Total firewater pumping capacity shall exceed firewater system distribution requirements determined in Section 5.3. The pumping capacity will provide adequate duplication of pumps to ensure that firewater requirements can be provided under adverse operating conditions.

A minimum of two pumps shall be provided to furnish the total firewater pumping capacity at the required pressure. Multiple pumping units with different types of drivers shall be installed to improve reliability. The total firewater capacity shall be rounded off to match a standard pump size based on two or more pumps. Four or more pumps of the same size in the size range from 1500 to 2500 gpm at design pressure is the recommended practical and reliable cost effective design.

An adequate number of internal–combustion engine (diesel) driven fire pumps shall be provided to supply the firewater system requirements determined in Section 5.3. Electric or steam turbine driven fire pump may be provided to supplement the internal combustion engine (diesel) driven fire pumps and meet total firewater pumping capacity requirements of Section 7.1. The use of supplemental internal combustion (diesel) driven fire pumps shall be given priority when evaluating supplemental fire pumps to reduce reliance on other plant services.

A jockey pump or connection from a utility water pump shall be provided to maintain a uniform water pressure on the firewater main system. The jockey pump shall be sized for at least 100 gpm at a residual design pressure of 100 psig per paragraph 6.1.1. A UL–approved Back–Flow Preventer shall be used to prevent contamination of a utility water system or loss of firewater when higher–pressure fire pumps are put into operation. Firewater main pressure shall be monitored at a continuously manned location and alarm upon low pressure in the system.

A suitable enclosure (wire fence or building) and warning signs shall be provided on automatic starting or remote controlled fire pumps.

FIRE MAIN AND HYDRANTS ARRANGEMENTS

MONITORS

Monitors shall be used when they can be located so as to protect more than one item of process equipment from their installed position, or where their use is more effective than a fixed water spray system for fire fighting. Monitors are effective for cooling fire-exposed equipment, as well as for fire intensity control. They can be used to flush burning flammable liquids away from equipment, provided care is taken not to spread the fire. Portable monitors provide additional flexibility in fire control operations and can be provided for supplemental water cooling.

Water monitors have the following limitations:

Multiple monitors supplied by a non–looped branch line, mains exceeding 200 feet or nozzle capacities exceeding 500 gpm shall be connected by 6-inch pipe. Shutoff valves at the monitor shall be NPS 4 ball–type. An indicator shutoff valve and automatic below grade drain valve shall be installed in freezing climates. All valves shall be clearly identified with weather resistant signs.

Portable monitors shall be provided in each plant as follows:

10.0 TABLES

TABLE 1

PROCESS UNIT FIREWATER REQUIREMENTS

Type of Process Unit Minimum Firewater Demand (US gpm)
Atmospheric distillation, vacuum, or combination units with up to 100,000 bpcd throughput; treating plants; asphalt stills; others 5000
Atmospheric distillation, vacuum, or combination units with 100,000 bpcd or higher throughput; catalytic cracking units 7000
Light–end units containing volatile oils and hydrogen, such as reformers, catalytic desulfurizers, Fluid catalytic crackers, high pressure units (over 1000 PSI) 9000
Lube oil units and blending (excluding propane extraction units) 4000

TABLE 2 FIREWATER MONITORS

Type of Unit or Equipment Application of Monitors
Process unit towers Insulated column–type vessels, reboilers, hot oil piping and bottom connections.
Heat exchanger banks containing high–pressure volatile or hot materials. Channel sections or expansion joints and flanged connections.
Process unit heaters Exposed return bends and crossovers, areas under heaters, structure cooling and spill wash down.
Process unit air coolers Coolers containing volatile liquids at over 250 psig or materials above autoignition temperature.
Offsite Class I or II hydrocarbon service position offsite pumps. Position one or two fixed water monitors to cover both pumps and adjacent pipe manifolds.
Pipeways and sleeperways Strategically placed fixed water monitors arranged to wash away spills and/or cool adjacent piping in event of fire under main pipeways and sleeperways vital to plant operation.

TABLE 3 FOAM/WATER MONITORS

Location Application of Monitors
Process units Minimum of two portable monitors provided for process area protection shall be foam/water type.
Tank fields For fighting diked enclosure fires, pipeway fires, and cone roof foam solution application rate of 0.16 gpm/ft 2 of tank liquid surface area. A foam/water monitor shall be provided for use with a fire truck to apply foam on tank fires.
Piers and wharves Fixed and portable foam/water monitors are recommended for fire protection on piers and wharves. At least one remotely controlled monitor should be installed.

TABLE 4 DOCUMENTATION REQUIREMENTS

Item Description Format As–Built
1 Written approval to permit use of this Practice in place of a more stringent jurisdictional requirement. See EP 2–5–2 N/A
2 Results of a hazard analysis of the facility. See EP 2–5–2 N/A
3 Pre-fire plans. See EP 2–5–2 N/A
4 Fire systems calculations, layout and arrangement. See EP 2–5–2 Yes
5 Results of firewater system inspections and tests. See EP 2–5–2 N/A
6 Vendor quotes for hydrants. See EP 2–5–2 N/A

11.0 FIGURES

Figure

Figure

Figure

Figure

Figure

Figure

Figure

Figure