Inflection Point Engineering Refractory and Insulation Curriculum

Hot Apply

Module from the Refractory and Insulation Curriculum curriculum.

Module 7 - Hot Insulation Installation · Learning Objectives · 1. Size pipe sections vs blocks vs blankets based on geometry · 2. Apply 50% staggered joints on multi-layer insulation · 3. Specify banding: 1/2" stainless, 12-in centers typical · 4. Select jacketing: aluminum for outdoor, stainless for corrosive · 5. Install weatherproofing + seal joints to reduce CUI risk · Insulation Fabrication Types

Form Use Installation Cost Insulation Loss Notes
Pipe section (pre-formed) Piping 1/2 to 36" Glue or bands Low Some Fast application
Board/block Flat surfaces Bands Low Some Vessels, tanks
Blanket Irregular shapes Pins, pads Medium Higher loss Valves, fittings
Removable pad Flange joints Straps High Low IPE-EP-11-3-6
Sprayed foam In-place applied Spray Medium Some Irregular shapes

Source: Refractory_Insulation_Curriculum_v1.xlsx · Sheet: Hot Apply