Inflection Point Engineering Process Safety Management Curriculum

LOPA SIL

Module from the Process Safety Management Curriculum curriculum.

Module 3 - LOPA and SIL (IEC 61511) · Learning Objectives · 1. Apply Layers of Protection Analysis (LOPA) for specific scenarios · 2. Compute unmitigated frequency * PFD of IPLs < target TMEL · 3. Credit IPLs: BPCS (0.1), alarm + operator (0.1), relief (0.01) · 4. Determine SIL: SIL 1 (10-100 PFD), SIL 2 (100-1000), SIL 3 (1000-10000) · 5. Verify SIL via reliability calc (1oo2, 1oo3, MTBF, test interval) · Typical IPL Credits (CCPS LOPA)

IPL PFD Credit (logs) Conditions Notes Ref
BPCS (single loop, independent) 0.1 1 Independent from initiator Only one credit CCPS LOPA
Human response to alarm 0.1 1 Alarm rated, operator trained Not in the same loop as initiator CCPS
Relief valve (well-sized, maintained) 0.01 2 ASME coded, tested Not for fire exposure CCPS
Rupture disk 0.01 2 Sized correct One-shot CCPS
Check valve (well-maintained) 0.1 1 Testing, inspection Limited credit CCPS
SIF SIL 1 0.1-0.01 1-2 Fully engineered IEC 61511 IEC
SIF SIL 2 0.01-0.001 2-3 Fully engineered Test + diagnostic IEC
SIF SIL 3 0.001-0.0001 3-4 Redundancy, testing Rarely needed IEC
Mechanical interlock 0.01-0.001 2-3 Simple physical Gravity flow CCPS

Source: Process_Safety_Management_Curriculum_v1.xlsx · Sheet: LOPA SIL