Piping Engineering Curriculum
Module from the Piping Engineering Curriculum curriculum.
Module 10 — In-Service Piping Inspection (API 570) · Learning Objectives · 1. Classify piping circuits by consequence and apply API 570 Class 1/2/3 · 2. Set CML (condition monitoring location) density and inspection interval · 3. Compute corrosion rate (short-term, long-term) and remaining life · 4. Decide retirement thickness: greater of pressure design t_min or T/2 structural · 5. Prepare re-rate case per API 579 Level 1/2 when thinning approaches limit · API 570 Piping Classification & Inspection Frequency
| Class | Consequence | Example | Thickness Interval | Ext Visual Interval | Notes |
|---|---|---|---|---|---|
| Class 1 | High — flammable/toxic, high P/T | LPG, H2, H2S > 3% mol | 5 yr or 1/2 RL | 5 yr | RBI can extend |
| Class 2 | Moderate | HC < 650 °F, amine, hot oil | 10 yr or 1/2 RL | 5 yr | Standard refinery |
| Class 3 | Low — flammable off-plot, utilities | Low-P water, air, BFW | 10 yr or 1/2 RL | 10 yr | Lowest rigor |
| Class 4 | Optional non-hazard | Drainage, open vent | Per owner | Per owner | Sometimes excluded |
| Corrosion Rate & Remaining Life Formulas | |||||
| Short-term CR (in/yr) = (t_previous – t_actual) / (time between readings, yr). Long-term CR = (t_initial – t_actual) / (time since install, yr). Use the greater of short-term and long-term for remaining life: RL (yr) = (t_actual – t_min) / CR. Set next inspection at the lesser of: (a) max interval per Class and (b) RL/2. | |||||
| CML Selection Guidance (API 570 §5.5) | |||||
| Location | CML Rationale | Typical Count | Method | Notes | Ref |
| Straight runs | Baseline wall | 1 per 50 ft | UT thickness | Include elbow upstream | API 570 |
| Elbows | Erosion-corrosion hotspot | 4 quadrants each | UT grid | Extrados + intrados | API 570 |
| Tees & branches | Turbulence | 1 on branch, 1 on run | UT grid | Downstream side | API 570 |
| Reducers | Velocity change | 1 upstream, 1 downstream | UT | Local dead zones | API 570 |
| Deadlegs | NH4HS / corrosion | 100% UT bank | UT grid or RT | Re-examine after TA | API 570 §7.1.5 |
| Soil-air interface | External corrosion | 1 per crossing | UT or coupon | Coatings fail | API 570 §6.4.4 |
| Mixing points | Differential temp/chem | 4 pts downstream | UT | Jet impingement | API 570 |
| Injection points | Impingement wear | 12D downstream | UT grid | Inject sleeve recommended | API 570 §5.5.2 |
Source: Piping_Engineering_Curriculum_v1.xlsx · Sheet: In-Service
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.
© 2026 Inflection Point Engineering, LLC. All rights reserved.