Module 2 - Selection & Sizing

Module from the Instrumentation Engineering Curriculum curriculum.

INSTRUMENT SELECTION & SIZING · Learning Objectives · 1. Apply selection criteria based on process conditions (pressure, temperature, corrosion, hazardous area) 2. Size orifice plates using beta ratio and flow coefficient 3. Select materials of construction for process wetted parts 4. Specify instrument ranges with proper turndown and overrange · Selection Guide by Service Condition

Service Condition Pressure Temperature Flow Level Analytical Material Notes
Clean hydrocarbon liquid DP transmitter, gauge RTD or Type K TC Orifice, vortex, or Coriolis DP, radar, or displacer Density (Coriolis) 316 SS wetted parts standard
Dirty / slurry service Diaphragm seal transmitter Thermowell (heavy wall) Magnetic (if conductive), Coriolis Radar (non-contact), nuclear Sampling + lab analysis Hastelloy C-276 or ceramic
High temperature (>600°F) Remote seal with capillary Type K or N TC, thermowell Alloy 600 Orifice with remote seal taps DP with remote seals, radar Extractive sampling + cooling Alloy 625 or 800H thermowells
High pressure (>1500 psig) Monoflange DP, integral manifold TC in heavy-wall thermowell (Schedule 160) Orifice with 1500# flanges, Coriolis DP with monoflange, GWR Special sampling system NACE MR0175 if sour (SSC risk)
Corrosive (acid/caustic) Teflon-lined diaphragm seal Tantalum or Hastelloy thermowell Magnetic (PTFE liner), Coriolis (Hastelloy) Radar (PTFE antenna), ultrasonic pH, conductivity (specialty electrodes) Match alloy to corrodent
Cryogenic (<-50°F) Low-temp rated transmitter, seal fill rated for cryo Type T TC (best accuracy at cryo), RTD Coriolis, ultrasonic DP, GWR, radar Composition (GC, IR) 304/316 SS (avoid CS — brittle)
Hazardous area (Zone 1/Div 1) Explosion-proof or IS transmitter IS barriers for TC/RTD signals All types — must be rated for area class Same technologies — explosion-proof or IS IS analyzers or remote sampling FM/CSA/ATEX approval required
Source: IPE Engineering Practices Sec_12 (51 docs), Control Valve Handbook, Orifice_Flow_Calculator_v1.xlsx

Source: Instrumentation_Engineering_Curriculum_v1.xlsx · Sheet: Module 2 - Selection & Sizing