Instrumentation Engineering Curriculum
Module from the Instrumentation Engineering Curriculum curriculum.
INSTRUMENT SELECTION & SIZING · Learning Objectives · 1. Apply selection criteria based on process conditions (pressure, temperature, corrosion, hazardous area) 2. Size orifice plates using beta ratio and flow coefficient 3. Select materials of construction for process wetted parts 4. Specify instrument ranges with proper turndown and overrange · Selection Guide by Service Condition
| Service Condition | Pressure | Temperature | Flow | Level | Analytical | Material Notes |
|---|---|---|---|---|---|---|
| Clean hydrocarbon liquid | DP transmitter, gauge | RTD or Type K TC | Orifice, vortex, or Coriolis | DP, radar, or displacer | Density (Coriolis) | 316 SS wetted parts standard |
| Dirty / slurry service | Diaphragm seal transmitter | Thermowell (heavy wall) | Magnetic (if conductive), Coriolis | Radar (non-contact), nuclear | Sampling + lab analysis | Hastelloy C-276 or ceramic |
| High temperature (>600°F) | Remote seal with capillary | Type K or N TC, thermowell Alloy 600 | Orifice with remote seal taps | DP with remote seals, radar | Extractive sampling + cooling | Alloy 625 or 800H thermowells |
| High pressure (>1500 psig) | Monoflange DP, integral manifold | TC in heavy-wall thermowell (Schedule 160) | Orifice with 1500# flanges, Coriolis | DP with monoflange, GWR | Special sampling system | NACE MR0175 if sour (SSC risk) |
| Corrosive (acid/caustic) | Teflon-lined diaphragm seal | Tantalum or Hastelloy thermowell | Magnetic (PTFE liner), Coriolis (Hastelloy) | Radar (PTFE antenna), ultrasonic | pH, conductivity (specialty electrodes) | Match alloy to corrodent |
| Cryogenic (<-50°F) | Low-temp rated transmitter, seal fill rated for cryo | Type T TC (best accuracy at cryo), RTD | Coriolis, ultrasonic | DP, GWR, radar | Composition (GC, IR) | 304/316 SS (avoid CS — brittle) |
| Hazardous area (Zone 1/Div 1) | Explosion-proof or IS transmitter | IS barriers for TC/RTD signals | All types — must be rated for area class | Same technologies — explosion-proof or IS | IS analyzers or remote sampling | FM/CSA/ATEX approval required |
| Source: IPE Engineering Practices Sec_12 (51 docs), Control Valve Handbook, Orifice_Flow_Calculator_v1.xlsx |
Source: Instrumentation_Engineering_Curriculum_v1.xlsx · Sheet: Module 2 - Selection & Sizing
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.