Inflection Point Engineering Heat Exchanger Engineering Curriculum

Fouling

Module from the Heat Exchanger Engineering Curriculum curriculum.

Module 8 - Fouling and Cleaning · Learning Objectives · 1. Apply TEMA fouling resistance (Rf) by service type · 2. Select cleaning method: hydroblast, chemical, mechanical, sponge ball · 3. Diagnose fouling type: particulate, scale, biofouling, chemical, corrosion · 4. Monitor fouling with U trend, dP trend, and effluent temperature rise · 5. Size cleaning frequency by economic optimum (energy vs downtime) · TEMA Fouling Resistance Rf (hr-ft2-F/BTU)

Service Rf Equivalent h fouling Notes Cleaning Freq Ref
Steam (clean) 0.0005 2000 Minimum Never TEMA 9th
Distilled water 0.0005 2000 Rare TEMA
Treated cooling water 0.002 500 Most common Annual TEMA
Brackish water 0.003 333 6 months TEMA
Seawater 0.002-0.003 333-500 MIC issues 6 months TEMA
Light HC liquid 0.001 1000 Clean 2-3 yr TEMA
Gasoline, kerosene 0.001-0.002 500-1000 2 yr TEMA
Fuel oil 0.005 200 Heavier Annual TEMA
Vac tower bottoms 0.01+ 100 Coking Annual TEMA
Amine lean 0.002 500 18 mo TEMA
Amine rich 0.003 333 Foul Annual TEMA
Sour water 0.003 333 NH4HS Annual TEMA

Source: Heat_Exchanger_Engineering_Curriculum_v1.xlsx · Sheet: Fouling