Module 2 - Motors and Motor Control · Learning Objectives · 1. Apply NEMA MG 1 Design B/C/D torque characteristics · 2. Select IEEE 841 severe-duty motor for refinery service · 3. Size VFD for torque, speed range, and harmonic limits (IEEE 519) · 4. Compute full-load amps using NEC Table 430.250 (3-phase) and 430.248 (single) · 5. Apply service factor, temperature rise (Class B/F/H), and enclosure (TEFC, WPII, XP) · NEC Table 430.250 3-Phase Motor FLA (selected)
| HP | 115V | 230V | 460V | 2300V | Notes |
|---|---|---|---|---|---|
| 1/2 | 4.4 | 2.2 | 1.1 | - | Fractional |
| 5 | 28 | 15.2 | 7.6 | - | Small |
| 25 | - | 68 | 34 | - | Typical pump |
| 50 | - | 130 | 65 | - | Mid pump |
| 100 | - | 248 | 124 | - | Large pump |
| 200 | - | 312 | 156 | 33 | LV limit ~300HP |
| 500 | - | - | - | 79 | MV |
| 1000 | - | - | - | 155 | MV |
| Enclosure Type Selection | |||||
| Enclosure | IP Rating | Use | Outdoor? | Notes | NEMA |
| ODP (open drip proof) | IP22 | Indoor clean | No | Cheapest, dust risk | NEMA MG 1 |
| TEFC (totally enclosed fan cooled) | IP55 | Indoor/outdoor general | Yes | Most refinery pumps | Standard |
| WPII (weather protected) | IP24 | Outdoor sheltered | Yes | Large motors | Forced vent |
| XP (explosion proof) | IP66 | Div 1 Class I | Yes | Hazardous area | Certified |
| TENV (totally enclosed no vent) | IP55 | Small, intermittent | Yes | No fan | Smaller |
| Submersible | IP68 | Wet wells | Yes | Sewer/sump | Special |
Source: Electrical_Engineering_Curriculum_v1.xlsx · Sheet: Motors
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.