Commissioning and Startup Training Curriculum
Module from the Commissioning and Startup Training Curriculum curriculum.
Module 6 — Electrical and Motor Commissioning · Learning Objectives · 1. Execute safe energization of HV and LV equipment in correct sequence. · 2. Perform insulation resistance (megger) testing on motors and cables. · 3. Conduct solo run of motors and document bearing temperature, vibration, and current. · 4. Verify protective relay settings and coordination. · 5. Apply NFPA 70E LOTO practices during commissioning work. · Energization Sequence
| Step | Action |
|---|---|
| 1 | Substation transformer energized from utility |
| 2 | Switchgear bus energized; protective relays armed |
| 3 | MCC lineup energized |
| 4 | Individual motor feeders energized |
| 5 | VFD drives commissioned with motor decoupled |
| 6 | Motor solo run decoupled |
| 7 | Motor coupled, run with equipment no-load/low-load |
| Insulation Resistance (Megger) Criteria | |
| Voltage Class | Test Voltage |
| <600 V | 500 V DC |
| 600 V–4.16 kV | 1000 V DC |
| >4.16 kV | 5000 V DC |
| Cables | Per class |
| PI (Polarization Index) | 10-min/1-min |
| Motor Solo Run — Data Logged | |
| Parameter | Acceptance |
| Rotation | Per arrow; verify before coupling |
| No-load amps | ~30–40% of FLA |
| Bearing temperature | <185 °F (85 °C) steady state |
| Bearing vibration | <0.157 in/s (4 mm/s) per ISO 10816 |
| Motor winding temp | <221 °F (105 °C) at full load |
| Run duration | 2 hours solo; then 4 hours coupled |
| Protective Relay — Typical Functions | |
| ANSI # | Function |
| 50/51 | Overcurrent |
| 27/59 | Under/over voltage |
| 49 | Thermal overload |
| 46 | Current unbalance / negative seq |
| 87 | Differential |
| 81 | Frequency |
| 51G / 50G | Ground fault |
| NFPA 70E Commissioning Practices | |
| Activity | Requirement |
| LOTO | De-energized work |
| Arc flash PPE | Per incident energy calc, labels posted |
| Qualified person | Training + recent exposure documented |
| Permit | Energized work permit for >50 V live work |
| Absence-of-voltage test | 3-point: test meter, prove on live, test circuit, prove again |
| ◄ Return to Instructions |
Source: Commissioning_and_Startup_Training_Curriculum_v1.xlsx · Sheet: Mod 6 - Electrical
© 2026 Inflection Point Engineering, LLC. All rights reserved. The content of this page — including calculation methods, reference data, written analysis, interactive tools, and source code — is the intellectual property of Inflection Point Engineering, LLC and is protected under applicable copyright, trademark, and trade secret laws. Unauthorized reproduction, redistribution, modification, or derivative use in whole or in part is prohibited without prior written consent.
Disclaimer. This material is provided for informational and educational purposes only and does not constitute professional engineering advice. Calculations, reference data, and methodologies are based on published standards and accepted engineering practice but are not a substitute for engineering judgment, site-specific analysis, or review by a licensed Professional Engineer. Inflection Point Engineering, LLC makes no warranties, express or implied, regarding the accuracy, completeness, or fitness for a particular purpose of any content presented here, and shall not be liable for any direct, indirect, incidental, or consequential damages arising from its use. Users assume all risk associated with applying this content to real-world design, operations, or decisions.
© 2026 Inflection Point Engineering, LLC. All rights reserved.