Electrical Load Summary

Connected, running, and demand electrical loads for plant MCC sizing. Paste one load per line (tag, rated_HP_or_kW, unit, voltage, eff%, PF, demand_factor, status). Computes full-load current, running kW, and demand kW per load plus totals.

Method: rated kW = HP × 0.7457 (if unit is HP); running kW = rated / efficiency; demand kW = running × demand factor; FLA (3-phase) = P · 1000 / (√3 · V · η · PF). Use: feeder and transformer sizing, MCC bucket layout, connected vs diversified load estimates for early electrical planning.